124
"LINK PARA.
ERROR"
47
475*
Continue
[When using
MELSECNET/10]
(1) The contents of the
network parameters
for the third link unit,
written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the third link unit
have not been written.
(3) The setting for the
total number of
stations is 0.
476*
[When using
MELSECNET/10]
(1) The contents of the
network parameters
for the fourth link unit,
written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the fourth link unit
have not been written.
(3) The setting for the
total number of
stations is 0.
(1) Write the
parameters
again and
check.
(2) Check the
station number
settings.
(3) Persistent
error
occurrence
may indicate a
hardware fault.
Consult your
nearest
Mitsubishi
representative,
explaining the
nature of the
problem.
477
A ink parameter error was
detected by the CC-Link
module.
(1) Write the
parameters in
again and
check.
(2) If the error
appears again,
there is a
problem with
the hardware.
Consult your
nearest
System
Service, sales
office or
branch office.
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
Summary of Contents for MELSEC-A A1SCPUC24-R2
Page 2: ......
Page 11: ...A 9 ...
Page 12: ...A 10 ...
Page 13: ...A 11 ...
Page 14: ...A 12 ...
Page 15: ...A 13 ...
Page 16: ...A 14 ...
Page 17: ...A 15 ...
Page 105: ...79 MEMO ...
Page 156: ...130 MEMO ...
Page 159: ......