121
"LINK PARA.
ERROR"
47
0
Continue
[When using
MELSECNET/(II)]
(1) When the link range
at a data link CPU
which is also a master
station (station
number = 00) is set by
parameter setting at a
peripheral device, for
some reason the data
written to the link
parameter area
differs from the link
parameter data read
by the CPU.
Alternatively, no link
parameters have
been written.
(2) The total number of
slave stations is set at
0.
(3) The head I/O number
of the network
parameters is
incorrect.
(1) Write the
parameters
again and
check.
(2) Check the
station number
settings.
(3) Check the
head I/O
number of the
network
parameters.
(4) Persistent
error
occurrence
may indicate a
hardware fault.
Consult your
nearest
Mitsubishi
representative,
explaining the
nature of the
problem.
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action