96
Table 6.2 Error Code List for A1SHCPU and A2SHCPU (Continue)
Error
Message
Error
Code
(D9008)
Detailed
Error
Code
(D9092)
CPU
States
Error and Cause
Corrective Action
"INSTRCT.
CODE ERR"
(Checked at
STOP
RUN.)
10
103
Stop
Device specified by a
dedicated instruction
for CC-Link is not
correct.
Read the error step
using a peripheral
device and correct the
program of the step.
104
A dedicated instruction
for CC-Link has
incorrect program
structure.
105
A dedicated instruction
for CC-Link has
incorrect command
name.
"PARAMETE
R ERROR"
(Checked at
power-on or
STOP/
PAUSE
RUN.)
11
—
Stop
The contents of
parameters of CPU
memory have changed
due to noise or the
improper loading of
memory.
(1) Load the memory
cassette correctly.
(2) Read the
parameter
contents of CPU
memory, check
and correct the
contents, and
write them to CPU
again.
"MISSING
END INS."
(Checked at
STOP
RUN.)
12
—
Stop
There is no
(
) instruction in
the program.
Write
instruction
at the end of program.
END
FEND
END