120
"SP.UNIT
ERROR"
(Checked at
execution of
the FROM/TO
instruction or
the dedicated
instructions
for special
function
modules.)
46
461
Stop or
Continue
(set by
para-
meter)
Module specified by the
/
instruction is not
a special function module.
Read the error step
using a peripheral
device and check
and correct
contents of the
/
instruction of the
step.
462
(1) Module specified by
the dedicated
instruction for special
function module is not
a special function
module or not a
corresponding
special function
module.
(2) A command was
issued to a CC-Link
module with function
version under B.
(3) A CC-Link dedicated
command was issued
to a CC-Link module
for which the network
parameters have not
been set.
(1) Read the error
step using a
peripheral
device and
check and
correct
contents of the
dedicated
instruction for
special
function
modules of the
step.
(2) Replace with a
CC-Link
module having
function
version B and
above.
(3) Set the
parameters.
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
FROM TO
FROM TO