107
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
"INSTRCT
CODE ERR"
(Checked
when STOP
RUN or at
execution of
instruction.)
10
107
STOP
(1) Index qualification is
specified for the
device numbers and
set values in the
instruction of timers
and counters.
(2) Index qualification is
specified at the label
number of the pointer
(P) provided to the
head of destination of
the , , ,
,
,
and
instructions or at the
label number of the
interrupt pointer (I)
provided to the head
of an interrupt
program.
Read the error step
using a peripheral
device and correct
the program of the
step.
108
Errors other than 101 to
107 mentioned above.
OUT
CJ
SCJ
CALL
CALLP
JMP
LEDA/B FCALL
LEDA/BBREAK