108
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
"PARA-
METER
ERROR"
(Checked at
power on and
at STOP/
PAUSE
RUN.)
11
111
STOP
Capacity settings of the
main and sub programs,
microcomputer program,
file register comments,
status latch, sampl-ing
trace and extension file
registers are not within the
usable range of the CPU.
Read parameters
in the CPU
memory, check the
contents, make
necessary
corrections and
write them again to
the memory.
112
Total of the set capacity of
the main and sub
programs, file register
comments, status latch,
sampling trace and
extension file registers
exceeds capacity of the
memory cassette.
113
Latch range set by
parameters or setting of
M, L or S is incorrect.
Read parameters
in the CPU
memory, check the
contents, make
necessary
corrections and
write them again to
the memory
114
Sum check error
115
Either of settings of the
remote RUN/PAUSE
contact point by
parameters, operation
mode at occurrence of
error, annunciator
indication mode, or STOP
RUN indication mode
is incorrect.
116
The MNET-MINI
automatic refresh setting
by parameters is
incorrect.
117
Timer setting by
parameters is incorrect.
118
Counter setting by
parameters is incorrect.