30
Parameter
Indica-
tion
Name
Outline
Factory
Setting
<EC
Version>
50
Zero current
detection level
Set the level at which the zero current
detection signal (Y13) is output.
0 to 200%
5%
51
Zero current
detection time
When the output current is at or below the zero
current detection level (Pr. 50) for longer than this
period (Pr. 51), the zero current detection signal
(Y13) is output.
0.05 to 1s
0.5s
52
Control panel
display data
selection
You can choose the data displayed on the
operation panel.
0: Output frequency
1: Output current
100: Set frequency during stop/output
frequency during operation
0
53
Frequency setting
operation selection
You can use the setting dial like a
potentiometer to perform operation.
0: Setting dial frequency setting mode
1: Setting dial potentiometer mode
0
54
FM (AM) terminal
function selection
You can choose the indicator connected to the
FM (AM) terminal.
0: Output frequency monitor
1: Output current monitor
0
55
Frequency
monitoring
reference
Set the reference value of frequency monitoring.
0 to 120Hz
60Hz
<50Hz>
56
Current monitoring
reference
Set the reference value of current monitoring.
0 to 50A
Rated
output
current
57
Restart coasting
time
- - -
58
Restart cushion
time
At power restoration after an instantaneous
power failure, you can restart the inverter without
the motor being stopped (with the motor
coasting).
The inverter begins to restart after this period
(Pr. 57) has elapsed after power restoration.
The inverter does not restart by setting "- - -".
"0" setting generally does not pose a problem but
you can adjust the time (0 to 5s, - - -) according
to the magnitude of the load.
When the restart coasting time (Pr. 57) has
elapsed, the output voltage is risen gradually.
Set this cushion time (0 to 60s).
Operation may be performed generally at the
factory setting, but you can adjust the time
according to the magnitude of the load.
1s
59
Remote setting
function selection
You can set the remote setting function which
is used when the operation panel is away from
the control box, for example.
0: Without remote setting function
1: With remote setting function
With frequency setting storage function
2: With remote setting function
Without frequency setting storage function
0