4.2 Setting the Parameters
4.2.1 Example: Changing the Pr. 7 setting from "5s" to "10s"
(For parameter details, refer to the instruction manual (detailed).)
1.
Confirm the RUN indication and operation
mode indication.
The inverter must be at a stop.
The inverter must be in the PU operation
mode. (Press the key.)
2.
Press the key to choose
the parameter setting mode.
MODE
MODE
PU
EXT
SET
5.
Turn the setting dial until the
desired value appears.
Example: To change setting
from "5" to "10"
6.
Press the key to set the value.
SET
MODE
RUN
PU
EXT
Flicker ... Parameter setting complete!!
3.
Turn the setting dial until the
desired parameter number appears.
Example: Pr. 7 "acceleration time"
By turning the setting dial , you can read another parameter.
SET
Press the key to show the setting again.
SET
Press the key twice to show the next parameter.
Display
Operation
The parameter
number read
previously
appears.
SET
4.
SET
After parameter setting is complete, press the key once to show the alarm
history or twice to return to the monitor display. To change the setting of another
parameter, perform the operation in above steps 3 to 6.
Press the key to read the
currently set value.
Example: "5" (factory setting) appears.
Error display?
•
If write was performed with "1" set in Pr. 77
•
If the operation panel does not have the write precedence (only for
the type with RS-485 function)
•
If write was performed during operation
•
If write was performed in the external operation mode
Remarks
•
If the setting has not been changed, the value does not flicker and the next
parameter number appears.
•
Either step 1 or 2 may be carried out first.
•
Convenient usage
You can read the parameter number and set value in order without needing
to choose the parameter setting mode in steps 1 and 2 and press the
SET
key after showing the desired parameter number.