7.5.3 Inverter FR-E800-E Communication Settings
Set the parameters of the communication settings with PU (operation panel or Parameter unit). An inverter reset
after the setting is required for the parameters of the communication settings.
Item
Parameter
Set Value
Remarks
Ethernet function selection 1
Pr.1427
5001
Ethernet function selection 2
Pr.1428
45237 (Default value)
Ethernet function selection 3
Pr.1429
45238 (Default value)
Ethernet function selection 4
Pr.1430
9999
Ethernet IP address 1
Pr.1434
0 to 255
*1
Ethernet IP address 2
Pr.1435
Ethernet IP address 3
Pr.1436
Ethernet IP address 4
Pr.1437
Subnet mask 1
Pr.1438
255 (Default value)
*1
*2
Subnet mask 2
Pr.1439
255 (Default value)
*1
*2
Subnet mask 3
Pr.1440
255 (Default value)
*1
*2
Subnet mask 4
Pr.1441
0 (Default value)
*1
*2
*1: Settings of the GOT can be changed. When changing the settings, also change the settings of the inverter.
*2: Change the settings depending on the operation environment.
7.5.4 Settings of Sample Screen
Station Number Switching
In this sample screen, station No. can be switched between 1 and 16 in the default setting. When switching to the
number other than 1 to 16 such as station number 17, please refer to "7.7
Changing the Inverter Network No. and
Station No.
" and change the settings according to the system configuration.
7.5.5 Precautions
When connecting GOT2000 to the inverter via CC-Link IE TSN, the value cannot be written to the link devices (RX,
RY, RWw, RWr) which the functions (signals) are assigned to by GOT.
Forward command is assigned to RYn0, and reverse command is assigned to RYn1. Therefore forward/reverse
command cannot be input by [Forward] and [Reverse] switches in the operation command screens (B-12120 and
B-12121) and [Auto measure] switch in [
Machine diag.(load char. meas.)
] screen (B-12310).
Change the link devices (RX, RY, RWw, RWr) of the master station to control the link devices (RX, RY, RWw, RWr)
value.
The screens below have the limitations in this sample screen.
Screen
Limitations
B-12120, B-12121
[Forward] or [Reverse] cannot be performed.
B-12310
[Auto measure] cannot be performed.
For the functions (signals) assigned to the link devices, please refer to "INVERTER FR-E800 Instruction Manual
(Communication)".