7.4.1 Controller Setting of GOT
(1) Controller Setting
Item
Set Value
Remarks
Manufacturer
MITSUBISHI ELECTRIC
Controller Type
MELSEC iQ-R,RnMT/NC/RT,CR800-D *1
I/F
Ethernet: Multi
*1: Change [Controller Type] according to the CPU.
QCPU: MELSEC iQ-L
LCPU: MELSEC-Q/QS, Q17nD/M/NC/DR/DSR, CRnD-700
(2) Detail Setting
Item
Set Value
Remarks
GOT NET No.
1
GOT Station
18
GOT Communication Port No.
5001
Retry (Times)
3
Startup Time (Sec)
3
Timeout Time (Sec)
3
Delay Time (ms)
0
(3) GOT Ethernet Setting
Item
Set Value
Remarks
Update GOT Ethernet Standard Port
Setting
Checked
GOT IP Address
192.168.3.18
Subnet Mask
255.255.255.0
Default Gateway
0.0.0.0
Peripheral S/W Communication Port No.
5015
Transparent Port No.
5014
(4)
Connected Ethernet Controller Setting
Host
Net No.
Station
Unit Type
IP Address
Port No.
Communication
1
*
1
1
RCPU *2
192.168.3.39
5006
UDP
*2: Change [Unit Type] according to the CPU.
QCPU: QnUD (P)V/QnUDE(H)
LCPU: LCPU
(5) Routing Information Settings
Routing information setting is required in order to connect to a different network. Set as below.
Transfer Net No.
Relay Net No.
Relay Station No.
CH1
2
1
1