Graphic Operation Terminal F940GOT
Sampling Mode 5
5-6
5.2.2
START COND.
Set the timing at which sampling is started. (Even if the sampling condition (trigger or constant
cycle) is satisfied, sampling is not performed if the start condition is not satisfied.)
•
Sampling start by trigger
When X, Y, M, S, T or C becomes ON (OFF
à
ON)
or OFF (ON
à
OFF)
,
sampling is started. (D, Z and V cannot be specified.)
•
Sampling start by time
The time can be set within the range of 1 second to 31 days, 23 hours, 59 minutes and 59
seconds. When the specified time has come, sampling is started.
u
u
u
u
Basic operation
TIME
SET
START COND.
Paragraph 5.2
Select "START
COND." on the
screen.
The SET CONDITION
screen is displayed.
DEVICE
Select "DEVICE".
The screen 1 is
displayed.
Select "TIME".
The screen 2 is
displayed.
1) Sampling start
by trigger
2) Sampling start by time
1)
2)
Display the
device input
keyboard.
Device symbol
Device No.
ENT
OFF -> ON
Execute
the input.
Change over
"OFF -> ON" and
"ON -> OFF".
Select a bit device among X, Y, M, S, T and C.
SET
Display the
ten-key pad.
0 to 9
Set date, hour, minute
and second.Set date,
hour, minute and second.
ENT
They are changed over alternately.
[ SET CONDITION ]
END
START COND.
M 0
DEVICE
SET
OFF->ON
Screen 1
[ SET CONDITION ]
END
START COND.
0d 0h 0m 0s
TIME
SET
Screen 2
Summary of Contents for F940GOT-LWD-E
Page 1: ...OPERATION MANUAL F940GOT SWD E F940GOT LWD E...
Page 4: ...Graphic Operation Terminal F940GOT 2...
Page 6: ...Graphic Operation Terminal F940GOT 4...
Page 8: ...Graphic Operation Terminal F940GOT 6...
Page 14: ...Graphic Operation Terminal F940GOT Contents vi...
Page 104: ...Graphic Operation Terminal F940GOT Alarm Mode 6 6 12...
Page 148: ...Graphic Operation Terminal F940GOT Creation of Display Screens 9 9 30...
Page 228: ...Graphic Operation Terminal F940GOT Changeover of Display Screen FX PCS DU WIN E 11 11 18...