101
MXZ-3F, 4F
The left lamp of
OPERATION IN-
DICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C.
board)
Condition
Remedy
Indoor/
outdoor unit
failure mode
recall function
LED1
LED2
OFF
None (Normal)
Lit
Lit
2-time blink
Outdoor power system
Lit
Lit
Overcurrent protection cut-out operates 3 con-
secutive times within 1 minute after the com-
pressor gets started, or converter protection
cut-out or bus-bar voltage protection cut-out
operates 3 consecutive times within 3 minutes
after startup.
• Check the connection of the com-
pressor connecting wire.
• Refer to 12-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
○
3-time blink
Discharge temperature thermistor
Lit
Once
A thermistor shorts or opens during
compressor running.
• Refer to 12-6. "Check of outdoor
thermistors".
○
Defrost thermistor
Lit
Once
Ambient temperature thermistor
Lit
Twice
Fin temperature thermistor
Lit
3 times
P.C. board temperature thermis-
tor
Lit
4 times
• Replace the outdoor control P.C.
board.
Outdoor heat exchanger tem-
perature thermistor
Lit
9 times
• Refer to 12-6. "Check of outdoor
thermistors".
4-time blink
Overcurrent
Once
Not lit
21 A current flows into power module.
• Reconnect compressor connector.
• Refer to 12-6. "How to check in-
verter/compressor".
• Check the stop valve.
—
5-time blink
Discharge temperature
Lit
Lit
The discharge temperature exceeds 115°C
during operation.
Compressor can restart if discharge tempera-
ture thermistor reads 80°C or less 3 minutes
later.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 12-6. "Check of LEV".
—
6-time blink
High pressure
Lit
Lit
The outdoor heat exchanger temperature ex-
ceeds 70°C during cooling or the indoor gas pipe
temperature exceeds 70°C during heating.
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
—
7-time blink
Fin temperature
3 times Not lit
The fin temperature exceeds 88°C during op
-
eration.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 12-6. "Check of outdoor
fan motor".
—
P.C. board temperature
4 times Not lit The P.C. board temperature exceeds 67°C
during operation.
8-time blink
Outdoor fan motor
Lit
Lit
A failure occurs 3 consecutive times within 30
seconds after the fan gets started.
• Refer to 12-6. "Check of outdoor
fan motor".
—
9-time blink
Outdoor control system
Lit
5 times Nonvolatile memory data cannot be read prop-
erly.
• Replace the outdoor control P.C. board.
○
10-time blink Low discharge temperature
protection
Lit
Lit
The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 39°C for more than 20 minutes.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 12-6. "Check of LEV".
—
11-time blink Communication error
between P.C. boards
Lit
6 times Communication error occurs between the out-
door control P.C. board and outdoor power P.C.
board for more than 10 seconds.
• Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
—
The communication between boards protec-
tion cut-out operates 2 consecutive times.
○
Current sensor
Lit
7 times A short or open circuit is detected in the cur-
rent sensor during compressor operating.
—
—
Current sensor protection cut-out operates 2
consecutive times.
○
Zero cross detecting circuit
5 times Not lit Zero cross signal cannot be detected while the
compressor is operating.
• Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
—
The protection cut-out of the zero cross
detecting circuit operates 10 consecutive
times.
○
Converter
5 times Not lit A failure is detected in the operation of the
converter during operation.
• Check the voltage of power supply.
• Replace the outdoor power P.C.
board.
—
Bus-bar voltage
5 times Not lit The bus-bar voltage exceeds 400 V or falls to
low level during compressor operating.
• Check the voltage of power supply.
• Replace the outdoor control P.C.
board.
14-time blink Refrigerant leakage
(Sensor detection)
Lit
Lit
1.Refrigerant leaks from the piping or the
heat exchanger in the indoor unit.
2.The following items are used around the
indoor unit.
• Spray (LP gas including Freon, and
whose main ingredient is propane and
butane)
• Aerosol insecticide (including ethanol)
• Air spray painting (including dichlo-
romethane)
• Charcoal (charcoal fire)
• Chemicals (such as ethanol)
• Turn off the power after the indoor
unit finishes its FAN operation.
(The FAN operation continues for 3
hours.)
• Check the indoor unit to detect the
part where refrigerant leaks.
• Repair the part where refrigerant
leaks.
• Turn on the power again.
• Replace the refrigerant sensor if
the problem is not fixed.
○
NOTE
: Blinking patterns of this mode differ from the ones of
Troubleshooting check table (12-4.).
OBH790D
Summary of Contents for SEZ-M-DA Series
Page 42: ...42 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790D ...
Page 44: ...44 MXZ 2F33VF2 ET1 MXZ 2F42VF2 ET1 MXZ 2F53VF2 ET1 OBH790D ...
Page 45: ...45 MXZ 2F33VF3 E1 MXZ 2F42VF3 E1 MXZ 2F53VF3 E1 OBH790D ...
Page 46: ...46 MXZ 2F33VF3 ET1 MXZ 2F42VF3 ET1 MXZ 2F53VF3 ET1 OBH790D ...
Page 47: ...47 MXZ 2F53VFH E1 OBH790D ...
Page 49: ...49 MXZ 2F53VFH3 E1 OBH790D ...
Page 50: ...50 MXZ 3F54VF E1 ET1 E2 ET2 MXZ 3F68VF E1 ET1 E2 ET2 OBH790D ...
Page 52: ...52 MXZ 3F54VF2 ET1 MXZ 3F68VF2 ET1 OBH790D ...
Page 53: ...53 MXZ 3F54VF3 E1 MXZ 3F68VF3 E1 OBH790D ...
Page 54: ...54 MXZ 3F54VF3 ET1 MXZ 3F68VF3 ET1 OBH790D ...
Page 55: ...55 MXZ 4F72VF E1 ET1 E2 ET2 OBH790D ...
Page 57: ...57 MXZ 4F72VF2 ET1 MXZ 4F80VF2 ET1 OBH790D ...
Page 58: ...58 MXZ 4F72VF3 E1 MXZ 4F80VF3 E1 OBH790D ...