3. Table of outdoor unit failure mode recall function
MXZ-2F
Upper or
left lamp of
OPERATION
INDICATOR
lamp (Indoor
unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition
Remedy
Indoor/
outdoor
unit failure
mode
recall
function
LED 1
LED 2
OFF
None (Normal)
Not lit
Not lit
—
—
—
2-time blink
Outdoor power system
Lit
Lit
Overcurrent protection cut-out operates
3 consecutive times within 1 minute after
the compressor gets started.
Compressor protection cut-out
operates 24 consecutive times within
10 seconds after the compressor gets
started.
• Check the compressor connecting
wire.
• Refer to 12-6. "How to check
inverter/compressor".
• Check the stop valve.
○
3-time blink
Discharge temperature
thermistor
Lit
Once
Thermistor shorts or opens during
compressor running.
• Refer to 12-6. "Check of out-
door thermistors".
○
Defrost thermistor
Lit
Once
○
Ambient temperature
thermistor
Lit
Twice
○
Fin temperature thermistor
Lit
3 times
○
P.C. board temperature
thermistor
Lit
4 times
• Replace the inverter P.C. board.
○
Outdoor heat exchanger
temperature thermistor
Lit
9 times
• Refer to 12-6. "Check of out-
door thermistors".
○
4-time blink
Overcurrent
Once
Not lit
The overcurrent flows into intelligent
power module.
• Check the compressor connecting
wire.
• Refer to 12-6. "How to check
inverter/compressor".
• Check the stop valve.
—
Compressor
Twice
Not lit
The overcurrent flows into intelligent
power module within 10 seconds after
the compressor gets started.
(The compressor gets restarted in
15 seconds.)
• Check the compressor connecting
wire.
• Refer to 12-6. "How to check
inverter/compressor".
—
9 times
Not lit
Waveform of compressor current is dis-
torted.
—
5-time blink
Discharge temperature
Lit
Lit
Discharge temperature exceeds 116ºC
during operation.
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 12-6. "Check of LEV".
—
6-time blink
High pressure
Lit
Lit
The outdoor heat exchanger temperature
exceeds 70ºC during cooling or the indoor
gas pipe temperature exceeds
70ºC during heating.
• Check the refrigerant circuit and
the refrigerant amount.
• Check the stop valve.
—
7-time blink
Fin temperature
3 times
Not lit
The fin temperature exceeds 90ºC
during operation.
• Check the around outdoor unit.
• Check the outdoor unit air pas-
sage.
—
P.C. board temperature
4 times
Not lit
The P.C. board temperature exceeds
80ºC during operation.
• Refer to 12-6. "Check of out-
door fan motor".
—
8-time blink
Outdoor fan motor
Lit
Lit
Failure occurs 3 consecutive times
within 30 seconds after the fan gets
started.
• Refer to 12-6. "Check of out-
door fan motor".
—
9-time blink
Nonvolatile memory data
Lit
5 times Nonvolatile memory data cannot be read
properly.
• Replace the inverter P.C. board.
○
Power module
7 times
Not lit
The output of the power module that drove
the compressor was shorted or the wind-
ing of the compressor was shorted.
• Refer to 12-6. "How to check
inverter/compressor".
○
10-time blink
Discharge temperature
Lit
Lit
The discharge temperature is kept
under 50ºC (COOL mode)/40ºC (HEAT
mode) for more than 40 minutes.
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 12-6. "Check of LEV".
—
11-time blink
Current sensor
8 times
Not lit
The sensor circuit of current of
compressor shorts or opens during
compressor operate.
• Replace the inverter P.C. board.
○
Bus-bar voltage
6 times
Not lit
The bus-bar voltage exceeds 430 V or
falls to 50 V or below during compres-
sor operating.
• Check the power supply.
• Replace the inverter P.C. board.
○
14-time blink
Stop valve
Lit
12 times The current of compressor is power
module is out of order.
• Check the stop valve.
• Check the refrigerant circuit and
the refrigerant amount.
○
Refrigerant leakage
(Sensor detection)
Lit
Lit
1. Refrigerant leaks from the piping or the
heat exchanger in the indoor unit.
2. The following items are used around the
indoor unit.
• Spray (LP gas including Freon, and
whose main ingredient is propane and
butane)
• Aerosol insecticide (including ethanol)
• Air spray painting (including dichlo-
romethane)
• Charcoal (charcoal fire)
• Chemicals (such as ethanol)
• Turn off the power after the in-
door unit finishes its FAN opera
-
tion.
(The FAN operation continues for 3
hours.)
• Check the indoor unit to detect
the part where refrigerant leaks.
• Repair the part where refrigerant
leaks.
• Turn on the power again.
• Replace the refrigerant sensor if
the problem is not fixed.
○
NOTE:
Blinking patterns of this mode differ from the ones of
Troubleshooting check table (12-4).
OBH790D
Summary of Contents for SEZ-M-DA Series
Page 42: ...42 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790D ...
Page 44: ...44 MXZ 2F33VF2 ET1 MXZ 2F42VF2 ET1 MXZ 2F53VF2 ET1 OBH790D ...
Page 45: ...45 MXZ 2F33VF3 E1 MXZ 2F42VF3 E1 MXZ 2F53VF3 E1 OBH790D ...
Page 46: ...46 MXZ 2F33VF3 ET1 MXZ 2F42VF3 ET1 MXZ 2F53VF3 ET1 OBH790D ...
Page 47: ...47 MXZ 2F53VFH E1 OBH790D ...
Page 49: ...49 MXZ 2F53VFH3 E1 OBH790D ...
Page 50: ...50 MXZ 3F54VF E1 ET1 E2 ET2 MXZ 3F68VF E1 ET1 E2 ET2 OBH790D ...
Page 52: ...52 MXZ 3F54VF2 ET1 MXZ 3F68VF2 ET1 OBH790D ...
Page 53: ...53 MXZ 3F54VF3 E1 MXZ 3F68VF3 E1 OBH790D ...
Page 54: ...54 MXZ 3F54VF3 ET1 MXZ 3F68VF3 ET1 OBH790D ...
Page 55: ...55 MXZ 4F72VF E1 ET1 E2 ET2 OBH790D ...
Page 57: ...57 MXZ 4F72VF2 ET1 MXZ 4F80VF2 ET1 OBH790D ...
Page 58: ...58 MXZ 4F72VF3 E1 MXZ 4F80VF3 E1 OBH790D ...