103
MXZ-2F
No. Symptom
Indication
Abnormal point / Con-
dition
Condition
Remedy
LED1(Red) LED2(Yellow)
1
Outdoor unit
does not op-
erate.
Lit
Once
LEV and drain pump
The indoor unit detects an abnormality in the LEV
and drain pump.
• Refer to 12-6. "Check of LEV".
• Check the drain pump of the indoor unit.
2
Lit
Twice
Outdoor power system
Overcurrent protection cut-out operates 3 consecu-
tive times within 1 minute after the compressor gets
started.
• Check the connection of the compressor connect-
ing wire.
• Refer to 12-6. "How to check inverter/compres-
sor".
• Check the stop valve.
3
Lit
3 times
Discharge temperature
thermistor
A short circuit is detected in the thermistor during
operation, or when an open circuit is detected in the
thermistor after 10 minutes of compressor startup.
• Refer to 12-6. "Check of outdoor thermistors".
4
Lit
4 times
Fin temperature
thermistor
A short or open circuit is detected in the thermistor
during operation.
• Refer to 12-6. "Check of outdoor thermistors".
P.C board temperature
thermistor
• Replace the inverter P.C. board.
5
Lit
5 times
Ambient temperature
thermistor
A short or open circuit is detected in the thermistor
during operation.
• Refer to 12-6. "Check of outdoor thermistors".
Outdoor heat ex-
changer temperature
thermistor
A short circuit is detected in the thermistor during
operation, or when an open circuit is detected in
the thermistor after 5 minutes (in cooling) and 10
minutes (in heating) of compressor startup.
Defrost thermistor
A short circuit is detected in the thermistor during
operation, or when an open circuit is detected in the
thermistor after 5 minutes of compressor startup.
6
Lit
7 times
Nonvolatile memory
data
The nonvolatile memory data cannot be read prop-
erly.
• Replace the inverter P.C. board.
7
Lit
11 times
Stop valve
Closed valve
Closed valve is detected by compressor current.
(
MXZ-2F33VF, MXZ-2F33VF2, MXZ-2F33VF3
)
• Check the stop valve.
8
Lit
17 times
Outdoor refrigerant
system abnormality
A closed valve and air trapped in the refrigerant
circuit are detected based on the temperature
sensed by the indoor and outdoor thermistors and
the current of the compressor.
• Check for a gas leak in a connecting piping etc.
• Check the stop valve.
• Refer to 12-6. "Check of outdoor refrigerant
circuit".
9
Lit
18 times
Detection of refrigerant
(Indoor unit)
1. Refrigerant leaks from the piping or the heat
exchanger in the indoor unit.
2. The following items are used around the in-
door unit.
• Spray (LP gas including Freon, and whose
main ingredient is propane and butane)
• Aerosol insecticide (including ethanol)
• Air spray painting (including dichloromethane)
• Charcoal (charcoal fire)
• Chemicals (such as ethanol)
• Turn off the power after the indoor unit fin
-
ishes its fan operation.
(The fan operation continues for 3 hours.)
• Check the indoor unit to detect the part
where refrigerant leaks.
• Repair the part where refrigerant leaks.
• Turn on the power again.
• Replace the refrigerant sensor if the problem
is not fixed.
10
Lit
19 times
Abnormality of refriger-
ant leakage sensor
(Indoor unit)
The refrigerant sensor mounted on the indoor
unit does not work.
The refrigerant sensor is not connected prop-
erly or the wire is broken.
• Connect the connector of the refrigerant sen-
sor properly.
• Replace the refrigerant sensor.
11
Lit
20 times
Incompatible unit com-
bination error
The indoor unit which is not compatible with
the outdoor unit is connected.
• Replace the indoor unit with the one which is
compatible with the outdoor unit.
12
'Outdoor unit
s t o p s a n d
r e s t a r t s 3
minutes later'
is repeated.
Twice
Not lit
Overcurrent
14 A (
MXZ-2F33VF, MXZ-2F33VF2, MXZ-
2F33VF3
)/18 A (
MXZ-2F42VF, MXZ-2F42VF2,
MXZ-2F42VF3, MXZ-2F53VF/VFH, MXZ-
2F53VF2/VFH2, MXZ-2F53VF3/VFH3
) current
flows into intelligent power module.
• Reconnect compressor connector.
• Refer to 12-6. "How to check inverter/
compressor".
• Check the stop valve.
13
3 times
Not lit
Discharge
temperature
protection
Discharge temperature exceeds 116°C during
operation. Compressor can restart if discharge
temperature thermistor reads 100°C or less 3
minutes later.
• Check the amount of gas and the refrigerant
circuit.
• Refer to 12-6. "Check of LEV".
14
4 times
Not lit
Fin temperature
protection
The fin temperature exceeds 90°C during operation.
• Check the refrigerant circuit and the refrigerant
amount.
• Refer to 12-6. "Check of outdoor fan motor".
P.C. board temperature
protection
The P.C. board temperature exceeds 78°C during
operation.
15
5 times
Not lit
High pressure protec-
tion
The outdoor heat exchanger temperature exceeds
70°C during cooling or indoor gas pipe temperature
exceeds 70°C during heating.
• Check the amount of gas and the refrigerant cir-
cuit.
• Check the stop valve.
16
9 times
Not lit
Bus-bar voltage
protection
The bus-bar voltage exceeds 430 V or falls to 50 V
or below during compressor operating.
• Replace the inverter P.C. board.
17
13 times
Not lit
Outdoor fan motor
Failure occurs 3 consecutive times within 30 sec-
onds after the fan gets started.
• Refer to 12-6. "Check of outdoor fan motor".
18
8 times
Not lit
Current sensor
protection
A short or open circuit is detected in the
current sensor during compressor operating.
• Replace the inverter P.C. board.
19
10 times
Not lit
Compressor
The compressor does not synchronize with the
operating power.
• Reconnect compressor connector.
• Refer to 12-6. "How to check inverter/
compressor".
• Check the stop valve.
12-4. TROUBLESHOOTING CHECK TABLE
OBH790D
Summary of Contents for SEZ-M-DA Series
Page 42: ...42 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790D ...
Page 44: ...44 MXZ 2F33VF2 ET1 MXZ 2F42VF2 ET1 MXZ 2F53VF2 ET1 OBH790D ...
Page 45: ...45 MXZ 2F33VF3 E1 MXZ 2F42VF3 E1 MXZ 2F53VF3 E1 OBH790D ...
Page 46: ...46 MXZ 2F33VF3 ET1 MXZ 2F42VF3 ET1 MXZ 2F53VF3 ET1 OBH790D ...
Page 47: ...47 MXZ 2F53VFH E1 OBH790D ...
Page 49: ...49 MXZ 2F53VFH3 E1 OBH790D ...
Page 50: ...50 MXZ 3F54VF E1 ET1 E2 ET2 MXZ 3F68VF E1 ET1 E2 ET2 OBH790D ...
Page 52: ...52 MXZ 3F54VF2 ET1 MXZ 3F68VF2 ET1 OBH790D ...
Page 53: ...53 MXZ 3F54VF3 E1 MXZ 3F68VF3 E1 OBH790D ...
Page 54: ...54 MXZ 3F54VF3 ET1 MXZ 3F68VF3 ET1 OBH790D ...
Page 55: ...55 MXZ 4F72VF E1 ET1 E2 ET2 OBH790D ...
Page 57: ...57 MXZ 4F72VF2 ET1 MXZ 4F80VF2 ET1 OBH790D ...
Page 58: ...58 MXZ 4F72VF3 E1 MXZ 4F80VF3 E1 OBH790D ...