2-4. CHOOSING THE OUTDOOR UNIT INSTALLATION LOCATION
R32 is heavier than air—as well as other refrigerants—
so tends to accumulate at the base (in the vicinity of the
floor). If R32 accumulates around base, it may reach a
flammable concentration in case room is small. To avoid
ignition, maintaining a safe work environment is required
by ensuring appropriate ventilation. If a refrigerant leak is
confirmed in a room or an area where there is insufficient
ventilation, refrain from using of flames until the work
environment can be improved by ensuring appropriate
ventilation.
Install outdoor units in a place where at least one of the
four sides is open, and in a sufficiently large space with-
out depressions.
2-5. MINIMUM INSTALLATION AREA
If you unavoidably install a unit in a space where all four sides are blocked or there are depressions, confirm that one of
these situations (A, B or C) is satisfied.
Note: These countermeasures are for keeping safety not for specification guarantee.
A) Secure sufficient installation space (minimum installation area Amin).
Install in a space with an installation area of Amin or more, corresponding to refrigerant quantity M (factory-charged
refri locally added refrigerant).
B) Install in a space with a depression height of 0.125 [m] or less.
OK
OK
OK
NG
Amin
Height from the bottom of
0.125 [m] or less
Height from the bottom of
0.125 [m] or less
M [kg]
Amin [m²]
1.0
12
1.5
17
2.0
23
2.5
28
3.0
34
3.5
39
4.0
45
4.5
50
5.0
56
5.5
62
6.0
67
6.5
73
7.0
78
7.5
84
OBH790D
Summary of Contents for SEZ-M-DA Series
Page 42: ...42 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790D ...
Page 44: ...44 MXZ 2F33VF2 ET1 MXZ 2F42VF2 ET1 MXZ 2F53VF2 ET1 OBH790D ...
Page 45: ...45 MXZ 2F33VF3 E1 MXZ 2F42VF3 E1 MXZ 2F53VF3 E1 OBH790D ...
Page 46: ...46 MXZ 2F33VF3 ET1 MXZ 2F42VF3 ET1 MXZ 2F53VF3 ET1 OBH790D ...
Page 47: ...47 MXZ 2F53VFH E1 OBH790D ...
Page 49: ...49 MXZ 2F53VFH3 E1 OBH790D ...
Page 50: ...50 MXZ 3F54VF E1 ET1 E2 ET2 MXZ 3F68VF E1 ET1 E2 ET2 OBH790D ...
Page 52: ...52 MXZ 3F54VF2 ET1 MXZ 3F68VF2 ET1 OBH790D ...
Page 53: ...53 MXZ 3F54VF3 E1 MXZ 3F68VF3 E1 OBH790D ...
Page 54: ...54 MXZ 3F54VF3 ET1 MXZ 3F68VF3 ET1 OBH790D ...
Page 55: ...55 MXZ 4F72VF E1 ET1 E2 ET2 OBH790D ...
Page 57: ...57 MXZ 4F72VF2 ET1 MXZ 4F80VF2 ET1 OBH790D ...
Page 58: ...58 MXZ 4F72VF3 E1 MXZ 4F80VF3 E1 OBH790D ...