105
MXZ-3F, 4F
No. Symptom
Indication
Abnormal point / Con-
dition
Condition
Remedy
LED1(Red) LED2(Yellow)
1 Outdoor
unit does
not operate.
Lit
Once
LEV and drain pump
The indoor unit detects an abnormality in the LEV
and drain pump.
• Refer to 12-6. "Check of LEV".
• Check the drain pump of the indoor unit.
2
Lit
Twice
Outdoor power
system
Overcurrent protection cut-out operates 3 consecu-
tive times within 1 minute after the compressor
gets started, or converter protection cut-out or bus-
bar voltage protection cut-out operates 3 consecu-
tive times within 3 minutes after startup.
• Check the connection of the compressor connect-
ing wire.
• Refer to 12-6. "How to check inverter/compres-
sor".
• Check the stop valve.
3
Lit
3 times
Discharge temperature
thermistor
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the ther-
mistor after 10 minutes of compressor startup.
• Refer to 12-6. "Check of outdoor thermistors".
4
Lit
4 times
Fin temperature
thermistor
A short or open circuit is detected in the thermistor
during operation.
• Refer to 12-6. "Check of outdoor thermistors".
P. C. board tempera-
ture thermistor
• Replace the outdoor control P.C. board.
5
Lit
5 times
Ambient temperature
thermistor
A short or open circuit is detected in the thermistor
during operation.
• Refer to 12-6. "Check of outdoor thermistors".
Outdoor heat ex-
changer temperature
thermistor
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the ther-
mistor after 5 minutes (in cooling) and 10 minutes
(in heating) of compressor startup.
Defrost thermistor
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the ther-
mistor after 5 minutes of compressor startup.
6
Lit
6 times
Zero cross detecting
circuit (Outdoor control
P.C. board)
Zero cross signal cannot be detected.
• Replace the outdoor control P.C. board.
7
Lit
7 times
Outdoor control system The nonvolatile memory data cannot be read
properly.
• Replace the outdoor control P.C. board.
8
Lit
8 times
Current sensor
Current sensor protection cut-out operates 2 con-
secutive times.
• Replace the outdoor power P.C. board.
9
Lit
11 times
Communication error
between P.C. boards
The communication protection cut-out between
boards operates 2 consecutive times.
• Check the connecting wire between outdoor con-
trol P.C. board and outdoor power P.C. board.
M-NET communication
error
M-NET adapter P.C. board detects an abnormality
in the communication error.
• Check the connecting wire between M-NET
adapter P.C. board and outdoor control P.C.
board, or terminal block.
10
Lit
12 times
Zero cross detecting
circuit (Outdoor power
P.C. board)
The protection cut-out of the zero cross detecting
circuit operates 10 consecutive times.
• Replace the outdoor power P.C. board.
11
Lit
13 times
Current sensor
A short or open circuit is detected in the input cur-
rent detection circuit during operation.
• Replace the outdoor power P.C. board.
12
Lit
14 times
Voltage sensor
A short or open circuit is detected in the input volt-
age detection circuit during operation.
• Replace the outdoor power P.C. board.
13
Lit
15 times
Relay operation
No relay operation is detected during operation.
• Replace the outdoor power P.C. board.
14
Lit
18 times
Detection of refrigerant
(Indoor unit)
1. Refrigerant leaks from the piping or the
heat exchanger in the indoor unit.
2. The following items are used around the
indoor unit.
• Spray (LP gas including Freon, and whose
main ingredient is propane and butane)
• Aerosol insecticide (including ethanol)
• Air spray painting (including dichlorometh-
ane)
• Charcoal (charcoal fire)
• Chemicals (such as ethanol)
• Turn off the power after the indoor unit fin
-
ishes its fan operation.
(The fan operation continues for 3 hours.)
• Check the indoor unit to detect the part
where refrigerant leaks.
• Repair the part where refrigerant leaks.
• Turn on the power again.
• Replace the refrigerant sensor if the problem
is not fixed.
15
Lit
19 times
Abnormality of refriger-
ant leakage sensor
(Indoor unit)
The refrigerant sensor mounted on the indoor
unit does not work.
The refrigerant sensor is not connected prop-
erly or the wire is broken.
• Connect the connector of the refrigerant sen-
sor properly.
• Replace the refrigerant sensor.
16
Lit
20 times
Incompatible unit com-
bination error
The indoor unit which is not compatible with
the outdoor unit is connected.
• Replace the indoor unit with the one which is
compatible with the outdoor unit.
17 'Outdoor unit
stops and
restarts
3 minutes
later' is
repeated.
Twice
Not lit
IPM protection
Overcurrent is detected after 30 seconds of com-
pressor startup.
• Reconnect compressor connector.
• Refer to 12-6. "How to check inverter/
compressor".
• Check the stop valve.
• Check the power module (PAM module).
Lock protection
Overcurrent is detected within 30 seconds of com-
pressor startup.
18
3 times
Not lit
Discharge temperature
protection
The discharge temperature exceeds 115°C during
operation.
Compressor can restart if discharge temperature
thermistor reads 80°C or less 3 minutes later.
• Check the amount of gas and refrigerant circuit.
• Refer to 12-6. "Check of LEV".
19
4 times
Not lit
Fin temperature
protection
The fin temperature exceeds during operation.
•Check refrigerant circuit and refrigerant amount.
•Refer to 12-6. "Check of outdoor fan motor".
P.C. board temperature
protection
The P.C. board temperature exceeds during opera-
tion.
20
5 times
Not lit
High pressure
protection
High pressure is detected with the high pressure
switch (HPS) during operation.
• Check around of gas and the refrigerant circuit.
• Check the stop valve.
The outdoor heat exchanger temperature exceeds
70°C during cooling or the indoor gas pipe tem-
perature exceeds 70°C during heating.
OBH790D
Summary of Contents for SEZ-M-DA Series
Page 42: ...42 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790D ...
Page 44: ...44 MXZ 2F33VF2 ET1 MXZ 2F42VF2 ET1 MXZ 2F53VF2 ET1 OBH790D ...
Page 45: ...45 MXZ 2F33VF3 E1 MXZ 2F42VF3 E1 MXZ 2F53VF3 E1 OBH790D ...
Page 46: ...46 MXZ 2F33VF3 ET1 MXZ 2F42VF3 ET1 MXZ 2F53VF3 ET1 OBH790D ...
Page 47: ...47 MXZ 2F53VFH E1 OBH790D ...
Page 49: ...49 MXZ 2F53VFH3 E1 OBH790D ...
Page 50: ...50 MXZ 3F54VF E1 ET1 E2 ET2 MXZ 3F68VF E1 ET1 E2 ET2 OBH790D ...
Page 52: ...52 MXZ 3F54VF2 ET1 MXZ 3F68VF2 ET1 OBH790D ...
Page 53: ...53 MXZ 3F54VF3 E1 MXZ 3F68VF3 E1 OBH790D ...
Page 54: ...54 MXZ 3F54VF3 ET1 MXZ 3F68VF3 ET1 OBH790D ...
Page 55: ...55 MXZ 4F72VF E1 ET1 E2 ET2 OBH790D ...
Page 57: ...57 MXZ 4F72VF2 ET1 MXZ 4F80VF2 ET1 OBH790D ...
Page 58: ...58 MXZ 4F72VF3 E1 MXZ 4F80VF3 E1 OBH790D ...