13 - 5
MELSEC-Q
13 COMMON FUNCTIONS
13.3 Execution data backup function
When the QD75MH buffer memory data is rewritten from the PLC CPU, "the data
backed up in the QD75MH flash ROM" may differ from "the data (buffer memory data)
for which control is being executed".
In cases like these, the data being executed will be lost when the PLC power is turned
OFF. (Refer to Chapter 7.)
In cases like these, the "execution data backup function" backs up the data being
executed by writing it to the flash ROM. The data that was backed up is then written to
the buffer memory when the power is turned ON next.
The details shown below explain about the "execution data backup function".
[1] Execution data backup means
[2] Control details
[3] Precautions during control
[4] Execution data backup method
[1] Execution data backup (written to flash ROM) means
• The backup is executed with a PLC program.
• The backup is executed by peripheral device.
Refer to GX Configurator-QP Operating Manual for execution data backup
method by peripheral device.
[2] Control details
The following shows the data that can be written to the flash ROM using the
"execution data backup function".
Buffer memory
Flash ROM
Parameters ( Pr.1
to Pr.57 , Pr.80
to
Pr.84 )
Parameters ( Pr.1
to Pr.57 , Pr.80
to
Pr.84 )
Positioning data (No. 1 to 600)
Positioning data (No. 1 to 600)
Block start data (No. 7000 to 7004)
Block start data (No. 7000 to 7004)
Servo parameters ( Pr.100 , to Pr.204 )
Servo parameters ( Pr.100 , to Pr.204 )
[3] Precautions during control
(1) Data can only be written to the flash ROM when the positioning control is not
carried out (when the PLC READY signal (Y0) is OFF).
(2) Writing to the flash ROM can be executed up to 100,000 times.
If writing to the flash ROM exceeds 100,000 times, the writing may become
impossible, and a "flash ROM writing error (error code: 801)" will occur.
(3) After one power ON/PLC CPU reset operation, writing to the flash ROM
using a PLC program is limited to up to 25 times.
If the 26th writing is executed, a "flash ROM write number error (error code:
805)" will occur. If this error occurs, carry out the power OFF ON/PLC
CPU reset operation again.
Refer to
Md.19
of Section 5.1.7 "Types and roles of monitor data" for
details.
Important
Do not turn the power ON/OFF, reset the PLC CPU, during writing to the flash
ROM. The flash ROM data may be corrupted.
Summary of Contents for QD75MH1
Page 17: ...A 16 MEMO ...
Page 19: ...MEMO ...
Page 66: ...3 11 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS MEMO ...
Page 97: ...4 18 MELSEC Q 4 INSTALLATION WIRING AND MAINTENANCE OF THE PRODUCT MEMO ...
Page 102: ...5 5 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 110: ...5 13 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 116: ...5 19 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 120: ...5 23 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 124: ...5 27 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 158: ...5 61 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 196: ...5 99 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 202: ...5 105 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 208: ...5 111 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 269: ...5 172 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 290: ...6 21 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 291: ...6 22 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 292: ...6 23 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 293: ...6 24 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 294: ...6 25 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 295: ...6 26 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 296: ...6 27 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 297: ...6 28 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 298: ...6 29 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 299: ...6 30 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 300: ...6 31 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 301: ...6 32 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 302: ...6 33 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 303: ...6 34 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 304: ...6 35 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 305: ...6 36 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 306: ...6 37 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 307: ...6 38 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 308: ...6 39 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 309: ...6 40 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 310: ...6 41 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 311: ...6 42 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 312: ...6 43 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 313: ...6 44 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 314: ...6 45 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 315: ...6 46 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 316: ...6 47 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 317: ...6 48 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 318: ...6 49 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 319: ...6 50 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 320: ...6 51 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 348: ...7 7 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 352: ...7 11 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 363: ...MEMO ...
Page 495: ...9 116 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 557: ...11 36 MELSEC Q 11 MANUAL CONTROL MEMO ...
Page 689: ...14 18 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 751: ...Appendix 2 MELSEC Q APPENDICES MEMO ...