11 MANUAL CONTROL
11.4.4 Creating a program to enable/disable the manual pulse generator operation
A PLC program must be created to execute a manual pulse generator operation.
Consider the "required control data setting", "start conditions" and "start time chart"
when creating the program.
The following shows an example when a manual pulse generator operation is started
for axis 1.
Required control data setting
The control data shown below must be set to execute a manual pulse generator
operation. The setting is carried out with the PLC program.
Buffer memory address
Setting item
Setting
value
Setting details
Axis
1
Axis
2
Axis
3
Axis
4
Cd.20
Manual pulse
generator 1 pulse
input magnification
1
Set the manual pulse generator 1 pulse input
magnification.
1522
1523
1622
1623
1722
1723
1822
1823
Cd.21
Manual pulse
generator enable
flag
1 (0)
Set "1: Enable manual pulse generator
operation". (Set "0: Disable manual pulse
generator operation" when finished with the
manual pulse generator operation.)
1524 1624 1724 1824
Refer to Section 5.7 "List of control data" for details on the setting details.
Start conditions
The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the PLC program, and the PLC program must be
configured so the operation will not start if the conditions are not fulfilled.
Device
Signal name
Signal state
Axis
1
Axis
2
Axis
3
Axis
4
PLC READY signal
ON PLC CPU preparation completed
Y0
QD75 READY signal
ON QD75MH preparation completed
X0
All axis servo ON
ON All axis servo ON
Y1
Synchronization flag ON
QD75MH buffer memory
The access is possible.
X1
Axis stop signal
OFF Axis stop signal is OFF
Y4
Y5
Y6
Y7
Start complete signal
OFF Start complete signal is OFF
X10 X11 X12 X13
BUSY signal
OFF QD75MH is not operating
XC
XD
XE
XF
Error detection signal
OFF There is no error
X8
X9
XA
XB
Interface
signal
M code ON signal
OFF M code ON signal is OFF
X4
X5
X6
X7
Forced stop input signal ON There is no forced stop input
–
Stop signal
OFF Stop signal is OFF
–
Upper limit (FLS)
ON Within limit range
–
External
signal
Lower limit (RLS)
ON Within limit range
–
If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking. If it is set to the synchronous mode, it must not be
inserted in the program for interlocking because it is turned ON when the PLC CPU executes
calculation.
Summary of Contents for QD75MH1
Page 17: ...A 16 MEMO ...
Page 19: ...MEMO ...
Page 66: ...3 11 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS MEMO ...
Page 97: ...4 18 MELSEC Q 4 INSTALLATION WIRING AND MAINTENANCE OF THE PRODUCT MEMO ...
Page 102: ...5 5 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 110: ...5 13 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 116: ...5 19 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 120: ...5 23 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 124: ...5 27 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 158: ...5 61 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 196: ...5 99 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 202: ...5 105 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 208: ...5 111 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 269: ...5 172 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 290: ...6 21 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 291: ...6 22 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 292: ...6 23 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 293: ...6 24 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 294: ...6 25 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 295: ...6 26 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 296: ...6 27 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 297: ...6 28 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 298: ...6 29 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 299: ...6 30 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 300: ...6 31 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 301: ...6 32 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 302: ...6 33 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 303: ...6 34 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 304: ...6 35 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 305: ...6 36 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 306: ...6 37 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 307: ...6 38 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 308: ...6 39 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 309: ...6 40 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 310: ...6 41 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 311: ...6 42 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 312: ...6 43 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 313: ...6 44 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 314: ...6 45 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 315: ...6 46 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 316: ...6 47 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 317: ...6 48 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 318: ...6 49 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 319: ...6 50 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 320: ...6 51 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 348: ...7 7 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 352: ...7 11 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 363: ...MEMO ...
Page 495: ...9 116 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 557: ...11 36 MELSEC Q 11 MANUAL CONTROL MEMO ...
Page 689: ...14 18 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 751: ...Appendix 2 MELSEC Q APPENDICES MEMO ...