15 - 10
MELSEC-Q
15 TROUBLESHOOTING
Classification
of errors
Error
code
Error name
Error
Operation status at error occurrence
Home
position
return (OPR)
220
Illegal near-point dog
signal
When the count method 1) or 2) –
machine home position return (OPR)
is started, the near-point dog is set to
"1: External input signal of servo
amplifier".
Home position return (OPR) is not
started.
300
Outside JOG speed
range
At the time of JOG starting, the JOG
speed comes out of a specified
range.
The JOG operation is not carried out
when the JOG speed is outside the
setting range at the time of JOG start.
JOG
operation or
inching
operation
errors
301
Inching movement
amount error
The inching movement amount
exceeds the JOG speed limit.
The inching operation is not carried
out when the inching movement
amount exceeds a JOG speed limit at
the time of inching start.
500
Illegal condition data
No.
The condition data No. is outside the
setting range when a block using the
condition data is started by a special
starting (conditional start, wait start,
simultaneous start, FOR (condition)).
(1 Condition data No. 10)
The operation is terminated.
<When blocks are started
simultaneously>
• The partner axis for simultaneous
start is BUSY.
501
Error before
simultaneous start
<When multiple axes are started and
controlled simultaneously>
• The partner axis for simultaneous
start is BUSY.
• The "Simultaneous start axis start
data No." of the start axis is 0 or is
outside the setting range.
• The "Simultaneous start axis start
data No." of those axes other than
the start axis is outside the setting
range.
At start: The system will not operate.
During operation:
The system stops
immediately.
502
Illegal data No.
• The positioning data No. tried to be
executed is outside the ranges of 1
to 600, 7000 to 7004, and 9001 to
9004.
• The designation of a JUMP
destination is executed currently.
• The designation of a JUMP
destination is outside the ranges of
1 to 600.
The positioning data is not executed.
Positioning
operation
errors
503
Command speed is
not set
• At the start of positioning, a current
speed (–1) is set for the command
speed of the positioning data to be
initially executed.
• The current speed is set by speed
control.
• The current speed is set for speed-
position switching control.
At the start of positioning, operation
does not start.
Summary of Contents for QD75MH1
Page 17: ...A 16 MEMO ...
Page 19: ...MEMO ...
Page 66: ...3 11 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS MEMO ...
Page 97: ...4 18 MELSEC Q 4 INSTALLATION WIRING AND MAINTENANCE OF THE PRODUCT MEMO ...
Page 102: ...5 5 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 110: ...5 13 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 116: ...5 19 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 120: ...5 23 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 124: ...5 27 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 158: ...5 61 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 196: ...5 99 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 202: ...5 105 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 208: ...5 111 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 269: ...5 172 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 290: ...6 21 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 291: ...6 22 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 292: ...6 23 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 293: ...6 24 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 294: ...6 25 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 295: ...6 26 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 296: ...6 27 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 297: ...6 28 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 298: ...6 29 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 299: ...6 30 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 300: ...6 31 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 301: ...6 32 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 302: ...6 33 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 303: ...6 34 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 304: ...6 35 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 305: ...6 36 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 306: ...6 37 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 307: ...6 38 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 308: ...6 39 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 309: ...6 40 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 310: ...6 41 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 311: ...6 42 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 312: ...6 43 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 313: ...6 44 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 314: ...6 45 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 315: ...6 46 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 316: ...6 47 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 317: ...6 48 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 318: ...6 49 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 319: ...6 50 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 320: ...6 51 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 348: ...7 7 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 352: ...7 11 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 363: ...MEMO ...
Page 495: ...9 116 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 557: ...11 36 MELSEC Q 11 MANUAL CONTROL MEMO ...
Page 689: ...14 18 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 751: ...Appendix 2 MELSEC Q APPENDICES MEMO ...