GB
Control at Initial Start-up
-10- Peak-demand control
Emergency Operation Mode
-11- Multiple system control
Control Method
-12- Automatic operation of pump for freeze-up protection
1. Natural
freeze-up
protection
Control method
Natural freeze-up protection based
on both the outside temperature
and the water temperature
Details
Pump start conditions
"Outside temperature is within ±1 ºC
of 1 ºC" OR "Inlet or outlet water
temperature is within ±1 ºC of 3 ºC"
Pump stop conditions
"Outside temperature is more than
±1ºC of 3 ºC" OR "Inlet or outlet
water temperature is more than
±1ºC of 5 ºC"
General idea about demand control in the system with a combination of a heat pump and a combustion-type hot water boiler.
→During peak-demand hours, the operation of the air conditioning units is given higher priority than that of the heat pump units.
The peak-demand control function is a function that restricts the maximum capacity of the units. The maximum operation
capacities of the units are restricted to specific levels relative to the maximum capacity of the units (= the compressors are
operating at the maximum rotation speed (100 Hz on the unit described in this manual)) being set as 100%.
100%
(100Hz)
The compressor will operate at the maximum rotation speed of 80 Hz.
80%
Preset value
1. Electrical wiring diagram
( * ) Main/Sub units and switch settings
SW2-9
( Multiple system)
Main unit (Unit to which the external
water temperature sensor is connected.)
ON
* The main unit is the unit to which an external water temperature sensor is connected.
External
water
temperature
sensor
Field-supplied dry contact
switch/relay or remote
controller (PAR-W31MAA) or
centralized controller (AE-200)
SW2-9: ON
Address: 1
SW2-6: OFF
SW2-9: ON
Address: 2
SW2-6: OFF
SW2-9: ON
Address: 1 + n
Inter-unit wiring
(M-NET line)
Main unit
Sub unit
"n"th unit
Unit (MAIN circuit)
PCB
Unit (MAIN circuit)
PCB
Sub unit
Unit (MAIN circuit)
PCB
0000001906.book 109 ページ 2018年7月19日 木曜日 午前7時22分
Summary of Contents for QAHV-N560YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 9: ... 2 HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 21: ... I Read Before Servicing 14 HWE1517A GB 0000001906 book 14 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 23: ... 16 HWE1517A GB 0000001906 book 16 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 53: ... 46 HWE1517A GB 0000001906 book 46 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 65: ... 58 HWE1517A GB 0000001906 book 58 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 77: ... 70 IV Remote Controller GB HWE1517A 0000001906 book 70 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 79: ... 72 HWE1517A GB 0000001906 book 72 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 85: ... 78 HWE1517A GB 0000001906 book 78 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 91: ... 84 HWE1517A GB 0000001906 book 84 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 121: ... 114 HWE1517A GB 0000001906 book 114 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 127: ... 120 HWE1517A GB 0000001906 book 120 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 173: ... 166 HWE1517A GB 0000001906 book 166 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 175: ... X Attachments 168 HWE1517A GB 0000001906 book 168 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 176: ......