External water temperature sensor TW-TH16E
1. Parts that are required to install an external water
temperature sensor
(1) External water temperature sensor
(2) Wiring to connect the sensor and the unit*
(3) Wiring terminals to connect the wiring to the sensor and
the terminal block on the unit
(Four for M4 screws)*
*Items (1) and (2) are field supplied.
2. Installing the external water temperature sensor
Install the external water temperature sensor where the
water pipes merge or on the load-side tank as shown in
the figure at right.
Install horizontally or vertically on top of the pipe.
When installing horizontally, make sure the wire faces
down.
3. Wiring the external water temperature sensor
Connect the external temperature sensor wiring to the terminal block in the control box on the unit as shown in the
figure below.
Wire specifications
Wire size
2-core cable Min. 1.25 mm
2
Type
CVVS or CPEVS
Maximum length 20 m
Horizontal installation
Vertical installation
Note
Sensor wire
External water temperature sensor
Control box
12-pin terminal block in the control box on the unit
Unit
50
48
T2
T1
A
· B-constant: 3460K
R 1/2
Sensor
Sensor properties
· Resistance: R=15KΩ±3% (0 °C)
Terminal block for connection to the sensor
M4 screws × 3
Terminal screws
A
BB
(Note)
Run the sensor wiring at least 5 cm away from any wire that
carries a voltage of 100 V or more, and do not put the sensor
wiring in the same conduit tube with it.
ø
78
54
42
157
20
12
ø
10
Ø
6
Connect the sensor wiring to terminals T1 and T2 of the 12-pin terminal
block in the control box on the unit.
Connect the shield to the earth terminal.
Cut the shield wire. Do not connect it to the terminal. (Connect the shield on the
unit side to the ground terminal.)
Detailed view of the area labeled "A" in the figure above
Shield (to be cut)
Field-supplied wire
Water-sealing rubber
(Internal diameter ø11)
Washer (Internal diameter ø12)
Tightening screw
(Internal diameter ø15)
1
2
4
3
5
6
Thread the wire to the external water temperature sensor through parts
through as shown in the figure at right. Attach M4 terminals
(field-supplied) to the wires, and connect them to and (terminals A and B).
2
4
5
6
After the wire is connected, securely tighten the tightening screw , and then
caulk the gap between the wire and the tightening screw to keep water
from entering.
4
1
0000001906.book 112 ページ 2018年7月19日 木曜日 午前7時22分
Summary of Contents for QAHV-N560YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 9: ... 2 HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 21: ... I Read Before Servicing 14 HWE1517A GB 0000001906 book 14 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 23: ... 16 HWE1517A GB 0000001906 book 16 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 53: ... 46 HWE1517A GB 0000001906 book 46 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 65: ... 58 HWE1517A GB 0000001906 book 58 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 77: ... 70 IV Remote Controller GB HWE1517A 0000001906 book 70 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 79: ... 72 HWE1517A GB 0000001906 book 72 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 85: ... 78 HWE1517A GB 0000001906 book 78 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 91: ... 84 HWE1517A GB 0000001906 book 84 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 121: ... 114 HWE1517A GB 0000001906 book 114 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 127: ... 120 HWE1517A GB 0000001906 book 120 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 173: ... 166 HWE1517A GB 0000001906 book 166 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 175: ... X Attachments 168 HWE1517A GB 0000001906 book 168 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 176: ......