II
Restrictions ]
- 28 -
HWE1517A
GB
3. Set the preset values with the switches on the circuit board.
(1) Set the dip switches SW2 and SW3 by following the procedure in
page 101. (Set the dip switches 3-8, 3-9, and 3-10 to ON.)
* [EEEE] will disappear, and an item code ([101]) will appear on LED1
(labeled B in the figure at right).
(2) Use SWP3 to toggle through the item codes and select an item code to
change its current value. (The item codes will appear in the following
order: [101]→[104]→[105]→[106]→ [107]....
(3) Use SWP1 to increase the value and SWP2 to decrease the value.
(4) Press SWP3 to save the changed value.
(5) Set the dip switches 3-8, 3-9, and 3-10 to OFF.
(6)
When connecting AE-200, perform the procedures described in 4 on
page 31.
Following the steps above, set the value for the following items as necessary.
[101] Not used
[104] Not used
[105] Function setting* (When AE-200 is not connected to QAHV, the values set by rotary switches SWU1 and
SWU2 are set as the preset values. When AE-200 is connected to QAHV, set the preset values referring to
the notes below.)
[106] Total number of units in the system (Initial value: 1) (Leave it as it is.)
[107] “2” when connected to AE-200 (Initial value: 0)
[108] Not used
[109] Not used
[110] Function setting (“1” when connected to AE-200) (Initial value: 0)
[111] M-NET address of main sensor of own tank (Initial value: 1)
[112 to 120] Not used
[121] Secondary side control is enabled when “1” is set. (Initial value: 0)
* When connecting AE-200 and remote controller (PAR-W31MAA) simultaneously, make the settings above, and
then turn off the power, turn it back on, and set “1” for item code [105]. After these settings, perform the
procedures described in (5) on page 32.
* Set SWS1 to OFF from the remote controller or with the local switch.
Settings cannot be changed unless the ON/OFF switch is set to OFF.
B
A
ON
1
23
456
789
1
0
ON
1
23
456
789
1
0
ON
1
23
456
789
1
0
10’s digit (0) 1’s digit (1)
(0)
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
0000001906.book 28 ページ 2018年7月19日 木曜日 午前7時22分
Summary of Contents for QAHV-N560YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 9: ... 2 HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 21: ... I Read Before Servicing 14 HWE1517A GB 0000001906 book 14 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 23: ... 16 HWE1517A GB 0000001906 book 16 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 53: ... 46 HWE1517A GB 0000001906 book 46 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 65: ... 58 HWE1517A GB 0000001906 book 58 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 77: ... 70 IV Remote Controller GB HWE1517A 0000001906 book 70 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 79: ... 72 HWE1517A GB 0000001906 book 72 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 85: ... 78 HWE1517A GB 0000001906 book 78 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 91: ... 84 HWE1517A GB 0000001906 book 84 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 121: ... 114 HWE1517A GB 0000001906 book 114 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 127: ... 120 HWE1517A GB 0000001906 book 120 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 173: ... 166 HWE1517A GB 0000001906 book 166 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 175: ... X Attachments 168 HWE1517A GB 0000001906 book 168 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 176: ......