VII
Control ]
- 93 -
HWE1517A
GB
Table 1
Primary side circuit flow rate map
(Check result)
4
-1
Check the following. (Primary side circuit)
Primary side circuit
↓
Check the checkbox.
□
All places with flow rate valve opening 1000 through 100 are 2 L or above?
If 2 L/min or below, air may not be bled out. Perform an air bleeding operation and water flow rate
adjustment operation again.
□
When there are multiple units, the values of the same pump output opening and the same valve opening
are not greater or less than those for other units by 10% and 2 L/min or more.
(In multiple-unit system, perform a water flow rate adjustment operation at the same time.)
□
All the values (item codes d01 through d09) are not “0” when the pump output opening is 16%. (Not
whole air is bled out.)
Table 2
Secondary side circuit flow rate map
(Check result)
4
-2
Check the following. (Secondary side circuit)
↓
Check the checkbox.
□
Is the output at 100% (d75) between 20 ℓ/min and 30 ℓ/min?
If the output is below 20 ℓ/min, water may not flow at a high flow rate during normal operation.
If the output is above 30 ℓ/min, water may not flow at a low flow rate during normal operation.
• Take a measure such as adjusting the frequency using an inverter, etc. so that the output at 100% (d75)
becomes between 20 ℓ/min and 30 ℓ/min.
□
Does a value from 1 ℓ/min to 4 ℓ/min exist for the flow rate at an arbitrary output except 0%?
If there was no value from 1 ℓ/min to 4 ℓ/min for the flow rate when any output except 0%, the flow rate
may not be able to be controlled at a low flow rate.
• Carry out the air bleeding and flow rate adjustment operations again.
• Take a measure such as adjusting the frequency using an inverter, etc. so that a value from 1 ℓ/min to 4 ℓ/min
exists for the flow rate during output.
Close
<------------------
Water flow rate adjust valve opening
------------------>
Open
Pump output opening/water flow rate
adjust valve opening
1600
1400
1200
1000
800
600
400
200
100
Flow rate (pump output opening 16%)
d01
d02
d03
d04
d05
d06
d07
d08
d09
Flow rate (pump output opening 27%)
d10
d11
d12
d13
d14
d15
d16
d17
d18
Flow rate (pump output opening 100%)
d19
d20
d21
d22
d23
d24
d25
d26
d27
Close
<------------------
Water flow rate adjust valve opening
------------------>
Open
Pump output opening/water flow rate
adjust valve opening
1600
1400
1200
1000
800
600
400
200
100
Flow rate (pump output opening 16%)
Flow rate (pump output opening 27%)
Flow rate (pump output opening 100%)
Pump output value
0
5
10
15
20
25
30
35
40
45
50
Flow rate
d55
d56
d57
d58
d59
d60
d61
d62
d63
d64
d65
Pump output value
55
60
65
70
75
80
85
90
95
100
Flow rate
d66
d67
d68
d69
d70
d71
d72
d73
d74
d75
Pump output value
0
5
10
15
20
25
30
35
40
45
50
Flow rate
Pump output value
55
60
65
70
75
80
85
90
95
100
Flow rate
0000001906.book 93 ページ 2018年7月19日 木曜日 午前7時22分
Summary of Contents for QAHV-N560YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 9: ... 2 HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 21: ... I Read Before Servicing 14 HWE1517A GB 0000001906 book 14 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 23: ... 16 HWE1517A GB 0000001906 book 16 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 53: ... 46 HWE1517A GB 0000001906 book 46 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 65: ... 58 HWE1517A GB 0000001906 book 58 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 77: ... 70 IV Remote Controller GB HWE1517A 0000001906 book 70 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 79: ... 72 HWE1517A GB 0000001906 book 72 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 85: ... 78 HWE1517A GB 0000001906 book 78 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 91: ... 84 HWE1517A GB 0000001906 book 84 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 121: ... 114 HWE1517A GB 0000001906 book 114 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 127: ... 120 HWE1517A GB 0000001906 book 120 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 173: ... 166 HWE1517A GB 0000001906 book 166 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 175: ... X Attachments 168 HWE1517A GB 0000001906 book 168 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 176: ......