2. System using a two-way valve
Notes on pump selection and connection
Select a pump in the same way as for a system with a three-way valve.
Notes on two-way valve selection and connection
• Use a valve that is capable of adjusting the flow rate with a 0 to 10 V input.
• Calculate the Cv value and select a valve that supports an appropriate rate.
• Select a valve of which the ratio of the maximum flow rate and the minimum flow rate will be at least 1:10.
• There are various kinds of two-way valve (such as ball valve, butterfly valve, and globe valve), and there are
valves suitable for flow rate adjustment and valves that are not suitable for flow rate adjustment. Therefore be
sure to select a two-way valve of a kind capable of precisely controlling the flow rate, such as a butterfly valve or
globe valve.
• Place the two-way valve downstream of the pump.
• Carefully read the instruction manual and use the two-way valve in accordance with the usage procedures.
3. System using an inverter
Notes on pump selection and connection
Select a pump in basically the same way as for a system with a three-way valve or two-way valve.
• Select a pump that can be used also at a low frequency (6 Hz or less).
(The motor may be seized depending on the pump selected as this control is performed at a low frequency.)
• Select a pump of which flow rate at 100% output is between 20 to 30 ℓ/min.
Notes on inverter selection and connection
• The inverter needs to be able to adjust output with a 0 to 10 input.
• Select an inverter that will not cause the seizing of the motor.
• Configure the settings so that the flow rate on the secondary side will become 0 ℓ/min when the unit is not
operating.
• Carefully read the instruction manual and use the inverter in accordance with the usage procedures.
Overview of system
This system has a pump provided at the outlet of the
tank and a two-way valve provided downstream of
the pump, and adjusts the flow rate by controlling the
opening and closing of the two-way valve.
Flow rate
output device
Flow rate
adjustment device
Pump
Two-way valve
Wiring
connection
places
1-3 of CN512 of
control board
(ON/OFF output)
Sub box
terminal block
No. 10, 11, 12
ON/OFF signal
0 to 10 V output
Two-way
valve
Pump
Overview of system
This system has a pump provided at the outlet
of the tank and an inverter connected to the
pump, and adjusts the flow rate by changing
the frequency of the inverter.
Flow rate
output
device
Flow rate
adjustment
device
Pump
Inverter
Wiring
connection
places
-
Sub box
terminal block
No. 10, 11, 12
0 to 10 V output
Pump
Inverter
0000001906.book 42 ページ 2018年7月19日 木曜日 午前7時22分
Summary of Contents for QAHV-N560YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 9: ... 2 HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 21: ... I Read Before Servicing 14 HWE1517A GB 0000001906 book 14 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 23: ... 16 HWE1517A GB 0000001906 book 16 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 53: ... 46 HWE1517A GB 0000001906 book 46 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 65: ... 58 HWE1517A GB 0000001906 book 58 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 77: ... 70 IV Remote Controller GB HWE1517A 0000001906 book 70 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 79: ... 72 HWE1517A GB 0000001906 book 72 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 85: ... 78 HWE1517A GB 0000001906 book 78 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 91: ... 84 HWE1517A GB 0000001906 book 84 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 121: ... 114 HWE1517A GB 0000001906 book 114 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 127: ... 120 HWE1517A GB 0000001906 book 120 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 173: ... 166 HWE1517A GB 0000001906 book 166 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 175: ... X Attachments 168 HWE1517A GB 0000001906 book 168 ページ 2018年7月19日 木曜日 午前7時22分 ...
Page 176: ......