Range Reference Table
The range reference tables are given below.
(1) Reference table for CH Industrial shipment settings offset/gain value
(Un\G202 to Un\G213)
The reference values change depending on the setting of Pass data classification set-
ting (Un\G200).
(2) Reference table for CH User range settings offset/gain value (Un\G214
to Un\G225)
[Example]
When using User range setting 3 in channel 1 and setting 1V to the offset value and
5V to the gain value, the following values are stored in the User range setting offset/
gain value areas.
• CH1 User range settings offset value (Un\G214): Approx. 9427
H
• CH1 User range settings gain value (Un\G215): Approx. E4C8
H
Address (Decimal)
Description
Pass data classification setting
Reference value
(Hexadecimal)
CH1
CH2
CH3
CH4
CH5
CH6
202
204
206
208
210
212
Industrial shipment
settings offset value
User range setting 1
0mA
Approx. 7FFF
H
User range setting 2
0V
Approx. 7FFF
H
User range setting 3
0V
Approx. 7FFF
H
203
205
207
209
211
213
Industrial shipment
settings gain value
User range setting 1
20mA
Approx. 24A0
H
User range setting 2
10V
Approx. E4C8
H
User range setting 3
5V
Approx. E4C8
H
Offset/gain value
Reference value
User range
setting 1
0mA
Approx. 7FFF
H
4mA
Approx. 6DB9
H
20mA
Approx. 24A0
H
User range
setting 2
-10V
Approx. 1B36
H
0V
Approx. 7FFF
H
10V
Approx. E4C8
H
User range
setting 3
0V
Approx. 7FFF
H
1V
Approx. 9427
H
5V
Approx. E4C8
H