6
- 4
6.2 For Use in Normal System Configuration
6.2.1 Before creating a program
6
PROGRAMMING
(2) Intelligent function module switch setting
Based on the setting conditions given in Section6.2 (2), make the intelligent function
module switch settings.
(a) Each switch setting
1) Switches 1 and 2: Output range setting
2) Switch3: HOLD/CLEAR setting function
3) Switch4: Mode setting
4) Switch5: Use prohibited (0:Fixed
*1
)
*1 If any other than 0 is set to Switch 5, an error occurs.
(b) Write the settings in (a) to the Q66DA-G.
On GX Developer’s “Parameter setting” screen, select the “I/O assignment” tab,
click “Switch setting”, and make settings of Switch 1 to 5 on the screen shown
below.
CH4 CH3 CH2 CH1
H
0 0 3 0
CH6 CH5
H
0: Fixed
0 0 0 0
CH1 :0
H
(4 to 20mA output)
CH2 :3
H
(0 to 5V output)
CH3 to CH6 :0
H
(Default)
<Switch 2>
<Switch 1>
H
0 0 0 0
b15
0: Fixed
0
b6
0
CH6
b5
0
CH5
b4
0
CH4
b3
0
CH3
b2
b2
0
CH2
b1
b1
b2 b1
0
CH1
b0
0
CH1 :0 (CLEAR)
CH2 :0 (CLEAR)
CH3 to CH6 :0 (Default)
<Switch 3>
H
0: Fixed
Setting of normal resolution mode / high resolution mode
All Channels: F
H
(high resolution mode)
Setting of normal mode / offset/gain setting mode
All Channels: F
H
(normal mode)
0 F 0 0
<Switch 4>
H
0: Fixed
0 0 0 0
<Switch 5>