4
- 9
4.5 Intelligent Function Module Switch Setting
4
SETUP AND PROCEDURES BEFORE OPERATION
4.5
Intelligent Function Module Switch Setting
The intelligent function module switches are set in the I/O assignment setting of GX Devel-
oper.
(1) Setting items
The intelligent function module switches, 1 to 5, are set using 16 bit data. The default
value for switches 1 to 5 is 0.
Table4.1 Switch setting item for intelligent function module
*1 Setting any value within the setting range provides the same operation.
When the setting range is 1
H
to F
H
, set 1
H
for example.
Setting item
Switch 1
Output range
setting(CH1to CH4)
Analog output range
Output range setting value
4 to 20 mA
0
H
0 to 20 mA
1
H
1 to 5 V
2
H
0 to 5 V
3
H
Switch 2
Output range setting
(CH5, CH6)
-10 to 10 V
4
H
4 to 20mA
(Extended mode)
A
H
1 to 5V
(Extended mode)
B
H
User range setting3
D
H
User range setting2
E
H
User range setting1
F
H
Switch 3
HOLD/CLEAR function setting
0: CLEAR
1: HOLD
Switch 4
Switch 5
0
H
: Fixed
CH4 CH3 CH2 CH1
H
CH6 CH5
H
00
H
: Fixed
CH6 CH5 CH4 CH3 CH2 CH1
b5 b4
b15
b6
to
b3 b2 b1 b0
0: Fixed
H
00
H
: Fixed
0
H
: Normal resolution mode
1
H
to F
H
(numeric value other than 0
H
)
*1
: High resolution mode
0
H
: Normal mode (D/A conversion processing)
1
H
to F
H
(numeric value other than 0
H
)
*1
: Offset/gain setting mode
Summary of Contents for Q66DA-G