5
- 24
5.6 Monitoring/Test
5.6.2 Offset/gain setting operation
5
UTILITY PACKAGE (GX Configurator-DA)
(5) Set up adjustment values
Set up an adjustment value of the offset value or gain value. Select "1", "10", "100", or
"1000" on the combo box, however, you can also set up adjustment values by enter-
ing a number (1 to 3000).
(6) Fine adjustment of voltage output or current output
By clicking the
button or
button, the value of voltage output or current output
for the prepared adjustment value is finely adjusted.
(7) Write settings into the Q66DA-G
Write the content set by operations (2) to (6) into the Q66DA-G by clicking the
button.
(a) Precautions
Do not perform the following operations during writing the content set by clicking
the
button into the module. If performed, an error occurs in Flash
memory data and the Q66DA-G may not operate properly.
• Power off the programmable controller CPU.
• Reset the programmable controller CPU.
(8) Switch to the normal mode
When the offset/gain setting screen is closed by clicking the
button after the
setting operation has finished, Q66DA-G’s operation mode transits to the normal
mode.
If an error code is displayed while performing the setting operation, the details and
measure of the error can be confirmed by clicking the
button to the right
of the error code display area. In addition, the error code can be cleared by click-
ing the
button.