96
OCH771
13-1. SMOOTH MAINTENANCE
13-1-1. <PAR-4xMAA ("x" represents 0 or later)>
Refer to "15-9. SMOOTH MAINTENANCE" for operation procedure.
Maintenance data, such as the indoor/outdoor unit’s heat exchanger temperature and compressor operation current can be
displayed with “Smooth maintenance”.
This cannot be executed during test operation.
Depending on the combination with the outdoor unit, this may not be supported by some models.
13 EASY MAINTENANCE FUNCTION
Smooth maintenance
Return:
Page
Ref.address
Cool
Sub cool
OU TH4 temp.
OU TH6 temp.
OU TH7 temp.
●
Reduces maintenance work drastically.
●
Enables you to check operation data of the indoor and outdoor units by remote controller.
Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even for
inverter models.
Remove the
service panel.
Measure
the intake air
temperature.
Measure the discharge
temperature.
Measure the outside
air temperature.
●Indoor unit ●
●Outdoor unit ●
Smooth Mainte-
nance Function
●
Conventional inspection work
Easy maintenance information (unit)
Compressor
Outdoor unit
Indoor unit
Accumulated operating
Heat exchanger
7
Intake air
time (
o
10 hours)
temperature (°C)
temperature (°C)
Number of ON/OFF
Discharge
8
4
5
1
2
9
6
3
Heat exchanger
times (
o
10 times)
temperature (°C)
temperature (°C)
Operating
Outside air
Filter operating
current (A)
temperature (°C)
time* (Hours)
* The filter operating time is the time that has elapsed since the filter was reset.
Discharge temperature 60°C