39
OCH771
10-3. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is put on>
Note: Refer to indoor unit section for codes starting with P and E.
Check Code Abnormal points and detection method
Cause
Judgment and action
None
―
1
No voltage is supplied to terminal
block (TB1) of outdoor unit.
a) Power supply breaker is turned
off.
b) Contact failure or disconnec-
tion of power supply terminal
c) Open phase (L, L2 or N phase)
2
Electric power is not supplied to
power supply terminal of outdoor
power circuit board.
a) Contact failure of power supply
terminal
b) Open phase on the outdoor
power circuit board
(Disconnection of terminal on
outdoor power circuit board)
3
Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4
Disconnection of reactor (DCL,
ACL4 or ACL)
5
Disconnection of outdoor noise
filter circuit board or parts failure
in outdoor noise filter circuit board
(ZM100–250Y)
6
Defective outdoor power circuit
board
7
Open of rush current protect
resistor (RS) (ZM100–250Y)
8
Defective outdoor controller circuit
board
1
Check following items.
a) Power supply breaker
b) Connection of power supply terminal
block. (TB1)
c) Connection of power supply terminal
block. (TB1)
2
Check following items.
a) Connection of power supply terminal
block. (TB1)
b) Connection of terminal on outdoor
power circuit board
3
Check
connection of the connector (CNDC)
on the outdoor controller circuit board.
Check
connection of the connector CNDC
on the outdoor power circuit board (ZM60–
140V)/noise filter circuit board (ZM100–
250Y). Refer to "10-8. TEST POINT
DIAGRAM".
4
Check
connection of reactor. (DCL, ACL4
or ACL)
Refer to "7. WIRING DIAGRAM".
5
a) Check connection of outdoor noise filter
circuit board.
b)
Replace outdoor noise filter circuit board.
Refer to "10-8. TEST POINT DIAGRAM".
6
Replace outdoor power circuit board.
7
Replace rush current protect resistor (RS)
Power circuit board might be short-circuit.
Check the power circuit board. (Refer to
"10-8. TEST POINT DIAGRAM".)
8
Replace controller board (When items
above are checked but the units cannot be
repaired.)
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open for
3 minutes continuously after power supply.
63H: High pressure switch
(ZM60-250)
TRS connector open
Abnormal if TRS connector circuit is open for
3 minutes continuously after power supply.
TRS:Thermal protector
(ZM200/250)
1
Disconnection or contact failure of
63H or TRS connector on outdoor
controller circuit board
2
Disconnection or contact failure of
63H or TRS
3
63H or TRS is working due to
defective parts.
4
Defective outdoor controller circuit
board
1
Check connection of 63H and TRS
connector on outdoor controller circuit
board.
Refer to "10-8. TEST POINT DIAGRAM".
2
Check the 63H and TRS side of connect-
ing wire.
3
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.
Summary of Contents for PUZ-ZM60VHA2
Page 23: ...23 OCH771 PUZ ZM60VHA2 ET ER UK PUZ ZM71VHA2 ET ER UK 7 WIRING DIAGRAM ...
Page 24: ...24 OCH771 PUZ ZM100VKA2 ET ER UK ...
Page 25: ...25 OCH771 PUZ ZM125VKA2 ET ER UK PUZ ZM140VKA2 ET ER UK ...
Page 26: ...26 OCH771 PUZ ZM100YKA2 ET ER UK PUZ ZM125YKA2 ET ER UK PUZ ZM140YKA2 ET ER UK ...