OCH771
Outdoor power circuit board
PUZ-ZM100YKA2(-ET/-ER).UK
PUZ-ZM125YKA2(-ET/-ER).UK
PUZ-ZM140YKA2(-ET/-ER).UK
Brief Check of POWER MODULE
If they are short-circuited, it means that they are broken.
Measure the resistance in the following points (connectors, etc.).
1. Check of DIODE MODULE
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note: The marks L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
CN5
Detection of primary
current (Connect to
the outdoor noise filter
circuit board (CNCT))
CN4
Connect to the
outdoor controller
circuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1
–
5
: Power circuit board
→
Transmitting
signal to the controller board (0–5 V DC)
2
–
5
: Zero cross signal (0–5 V DC)
3
–
4
: Not used
6
–
5
: 16 V DC
7
–
5
: 16 V DC
5
: –
1
,
2
,
6
,
7
: +
CN7
Connect to the outdoor con-
verter circuit board (CN7)
TB-U, TB-V, TB-W
Connect to the compressor (MC)
Voltage among phases:
10–400 V AC
TB-N
Connect to the CK capacitor
Diode module
U
P2
V
W
N2
L3
N1
L1
P1
L2
DIP-IPM
TAB connector
on X52CA
Connect to the
RS resistor
CN6
Thermistor
<Heat sink> (TH8)
TB-L1,
TB-L2,
TB-L3
Connect to the out-
door converter cir-
cuit board (L1-OU,
L2-OU, L3-OU)
400 V AC
L3OUT-L3IN
Lead connect