53
OCH771
Phenomena
Factor
Countermeasure
4. Even controlling by the wireless
remote controller, no beep is heard
and the unit does not start operating.
Operation display is indicated on
wireless remote controller.
The pair number settings of the wireless remote
controller and indoor controller board are mismatched.
Check the pair number settings.
5. When operating by the wireless
remote controller, beep sound is
heard, however, unit does not start
operating.
1
No operation for 2 minutes at most after the power
supply ON.
2
Local remote controller operation is prohibited.
• Remote controlling adaptor is connected to CN32 on
the indoor controller board.
• Local remote controller operation is prohibited by
centralized controller, etc. since it is connected to
MELANS.
3
Phenomena of No.2.
1
Normal operation
2
Normal operation
3
Check the phenomena No.2.
6. Remote controller display works
normally and the unit performs
cooling operation, however, the
capacity cannot be fully obtained.
(The air does not cool well.)
1
Refrigerant shortage
2
Filter clogging
3
Heat exchanger clogging
4
Air duct short cycle
1
•
If refrigerant leaks, discharging
temperature rises and LEV opening
increases. Inspect leakage by checking
the temperature and opening.
•
Check pipe connections for gas leakage.
2
Open intake grille and check the filter.
Clean the filter by removing dirt or dust on it.
3
•
If the filter is clogged, indoor pipe
temperature rises and discharging
pressure increases. Check if heat
exchanger is clogged by inspecting
discharging pressure.
•
Clean the heat exchanger.
4
Remove the blockage.
7. Remote controller display works
normally and the unit performs
heating operation, however, the
capacity cannot be fully obtained.
1
Linear expansion valve fault
Opening cannot be adjusted well due to linear
expansion valve fault.
2
Refrigerant shortage
3
Lack of insulation for refrigerant piping
4
Filter clogging
5
Heat exchanger clogging
6
Air duct short cycle
7
Bypass circuit of outdoor unit fault
1
•
Discharging temperature and indoor
heat exchanger temperature does not
rise.
Inspect the failure by checking
discharging pressure.
•
Replace linear expansion valve.
2
•
If refrigerant leaks, discharging
temperature rises and LEV opening
increases.
Inspect leakage by checking the
temperature and opening.
•
Check pipe connections for gas leakage.
3
Check the insulation.
4
Open intake grille and check the filter.
Clean the filter by removing dirt or dust on it.
5
•
If the filter is clogged, indoor pipe
temperature rises and discharging
pressure increases. Check if heat
exchanger is clogged by inspecting
discharging pressure.
•
Clean the heat exchanger.
6
Remove the blockage.
7
Check refrigerant system during
operation.
8.
1
For 3 minutes after temperature
adjuster turns off, the compressor
will not start operating even if
temperature adjuster is turned on.
2
For 3 minutes after temperature
adjuster turns on, the compressor
will not stop operating even if
temperature adjuster is turned off.
(Compressor stops operating
immediately when turning off by
the remote controller.)
12
Normal operation
(For protection of compressor)
12
Normal operation
Summary of Contents for PUZ-ZM60VHA2
Page 23: ...23 OCH771 PUZ ZM60VHA2 ET ER UK PUZ ZM71VHA2 ET ER UK 7 WIRING DIAGRAM ...
Page 24: ...24 OCH771 PUZ ZM100VKA2 ET ER UK ...
Page 25: ...25 OCH771 PUZ ZM125VKA2 ET ER UK PUZ ZM140VKA2 ET ER UK ...
Page 26: ...26 OCH771 PUZ ZM100YKA2 ET ER UK PUZ ZM125YKA2 ET ER UK PUZ ZM140YKA2 ET ER UK ...