28
OCH771
8
WIRING SPECIFICATIONS
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Notes: 1. Wiring size must comply with the applicable local and national code..
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
3. Install an earth line longer than power cables.
Warning:
In the case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
(Design 60245 IEC 57)
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
Power supply
Isolator
A-Control
Indoor Unit
Outdoor unit model
ZM60/71V
ZM100/125V
ZM140V
Outdoor unit power supply
~/N (single), 50 Hz, 230 V
~/N (single), 50 Hz, 230 V
~/N (single), 50 Hz, 230 V
Outdoor unit input capacity main switch (Breaker)
*1
25 A
32 A
40 A
Wiring
Wire No. × size (mm²)
Outdoor unit power supply
*5
3 × Min 2.5
3 × Min 4
3 × Min 6
Indoor unit-Outdoor unit
*2
3 × 1.5 (Polar)
3 × 1.5 (Polar)
3 × 1.5 (Polar)
Indoor unit-Outdoor unit earth
*2
1 × Min 1.5
1 × Min 1.5
1 × Min 1.5
Remote controller-Indoor unit
*3
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
Circuit rating
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
*4
230 VAC
230 VAC
230 VAC
Indoor unit-Outdoor unit S1-S2
*4
230 VAC
230 VAC
230 VAC
Indoor unit-Outdoor unit S2-S3
*4
28 VDC
28 VDC
28 VDC
Remote controller-Indoor unit
*4
12 VDC
12 VDC
12 VDC
Outdoor unit model
ZM100/125/140Y
ZM200/250Y
Outdoor unit power supply
3N~ (3 ph 4-wires), 50 Hz, 400 V
3N~ (3 ph 4-wires), 50 Hz, 400 V
Outdoor unit input capacity main switch (Breaker)
*1
16 A
32 A
Wiring
Wire No. × size (mm²)
Outdoor unit power supply
*5
5 × Min 1.5
5 × Min 4
Indoor unit-Outdoor unit
*2
3 × 1.5 (Polar)
Cable length 50m: 3 × 4 (Polar)/
Cable length 80m: 3 × 6 (Polar)
Indoor unit-Outdoor unit earth
*2
1 × Min 1.5
1 × Min 2.5
Remote controller-Indoor unit
*3
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
Circuit rating
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
*4
230 VAC
230 VAC
Indoor unit-Outdoor unit S1-S2
*4
230 VAC
230 VAC
Indoor unit-Outdoor unit S2-S3
*4
28 VDC
28 VDC
Remote controller-Indoor unit
*4
12 VDC
12 VDC
*1
A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
*2
(ZM100–140)
Maximum 45 m
If 2.5 mm² is used, maximum 50 m.
If 2.5 mm² is used and S3 is separated, maximum 80 m
Maximum 80 m. Total maximum including all indoor/indoor connection is 80 m.
*3
Maximum 500 m (When using 2 remote controllers, the maximum wiring length for the remote controller cables is 200 m.)
*4
The figures are NOT always against the ground.
S3 terminal has 28 VDC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
*5. In multi-phase appliances, the colour of the neutral conductor of the supply cord, if any, shall be blue.
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.