46
OCH771
Check Code Abnormal points and detection method
Cause
Judgment and action
E1
or
E2
Remote controller control board
1
Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board. (Check
code: E1)
2
Abnormal if the clock function of remote
controller cannot be normally operated.
(Check code: E2)
Defective remote controller
Replace remote controller.
E3
or
E5
Remote controller transmission error (E3)/
signal receiving error (E5)
1
Abnormal if remote controller could not
find blank of transmission path for 6
seconds and could not transmit.(Check
code: E3)
2
Remote controller receives transmitted
data at the same time, compares the data,
and when detecting it, judges different
data to be abnormal 30 continuous times.
(Check code: E3)
3
Abnormal if indoor controller board could
not find blank of transmission path.
(Check code: E5)
4
Indoor controller board receives
transmitted data at the same time,
compares the data, and when detecting
it, judges different data to be abnormal 30
continuous times. (Check code: E5)
1
2 remote controller are set as
“main.”
(In the case of 2 remote controllers)
2
Remote controller is connected
with 2 indoor units or more.
3
Repetition of refrigerant address
4
Defective transmitting receiving
circuit of remote controller
5
Defective transmitting receiving
circuit of indoor controller board
6
Noise has entered into
transmission wire of remote
controller.
1
Set a remote controller to main, and the
other to sub.
2
Remote controller is connected with only 1
indoor unit.
3
The address changes to a separate setting.
4
−
6
Diagnose remote controller.
a) When “RC OK” is displayed, remote
controllers have no problem.
Turn the power off, and on again to
check.
When becoming abnormal again,
replace indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00–66” is
displayed, noise may be causing
abnormality.
E6
(6840)
Indoor/outdoor unit communication error
(Signal receiving error)
1
Abnormal if indoor controller board could
not receive any signal normally for 6
minutes after turning the power on.
2
Abnormal if indoor controller board could
not receive any signal normally for 3
minutes.
3
Consider the unit as abnormal under
the following condition. When 2 or more
indoor units are connected to an outdoor
unit, indoor controller board could not
receive a signal for 3 minutes from
outdoor controller circuit board, a signal
which allows outdoor controller circuit
board to transmit signals.
1
Contact failure, short circuit or
miswiring (reversed wiring) of
indoor/outdoor unit connecting
wire
2
Defective transmitting receiving
circuit of outdoor controller circuit
board.
3
Defective transmitting receiving
circuit of indoor controller board.
4
Noise has entered into indoor/
outdoor unit connecting wire.
5
Defective fan motor
6
Defective rush current resistor of
outdoor power circuit board
Check LED display on outdoor controller
circuit board. (Connect A-Control service tool
(PAC-SK52ST))
Refer to EA−EC item if LED displays EA−AC.
1
Check disconnecting or looseness of
indoor /outdoor unit connecting wire of
indoor unit or outdoor unit.
Check all the units in the case of twin/
triple/quadruple indoor unit system.
2
–
4
Turn the power off, and on again to
check.
If abnormality occurs again, replace indoor
controller board or outdoor controller circuit
board.
Note: Other indoor controller board may have
defect in the case of twin/triple/quadruple
indoor unit system.
5
Turn the power off, and detach fan motor
from connector (CNF1, 2). Then turn the
power on again.
If abnormality is not displayed, replace fan
motor.
If abnormality is displayed, replace outdoor
controller circuit board.
6
Check the rush current resistor on outdoor
power circuit board with tester. If open is
detected, replace the power circuit board.
E7
Indoor/outdoor unit communication error
(Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
1
Defective transmitting receiving
circuit of indoor controller board
2
Noise has entered into power
supply.
3
Noise has entered into outdoor
control wire.
1
–
3
Turn the power off, and on again to
check. If abnormality occurs again,
replace indoor controller board.
E8
(6840)
Indoor/outdoor unit communication error
(Signal receiving error)
(Outdoor unit)
Abnormal if outdoor controller circuit board
could not receive anything normally for 3
minutes.
1
Contact failure of indoor/outdoor
unit connecting wire
2
Defective communication circuit of
outdoor controller circuit board
3
Defective communication circuit
of indoor controller board
4
Noise has entered into Indoor/
outdoor unit connecting wire.
1
Check disconnection or looseness of
Indoor/outdoor unit connecting wire of
indoor or outdoor units.
2
–
4
Turn the power off, and on again to
check. Replace indoor controller board
or outdoor controller circuit board if
abnormality is displayed again.