73
<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part ‘A-Control Service Tool (PAC-SK52ST)’ to connector
CNM on outdoor controller board.
[Display]
(1)Normal condition
Unit condition
Outdoor controller board
A-Control Service Tool
LED1 (Green)
LED2 (Red)
Check code
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
Lighted
Lighted
Lighted
Lighted
Lighted
Not lighted
Indication of the display
Alternately blinking display
Operation mode
Not lighted
Lighted
00, etc.
08, etc.
C5, H7 etc.
Indication
Error
Outdoor controller board
Contents
Check
code*
1
Inspection method
Detailed
reference
page
LED (Green) LED2 (Red)
1 blinking 2 blinking Connector (63H) is open.
F5
1
Check if connector (63H) on the outdoor controller board is not
disconnected.
2
Check continuity of pressure switch (63H) by tester.
P.32
2 blinking 1 blinking Miswiring of indoor/outdoor unit
connecting wire, excessive number
of indoor units (4 units or more)
―
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if 4 or more indoor units are connected to outdoor unit.
3
Check if noise entered into indoor/outdoor connecting wire or
power supply.
4
Re-check error by turning off power, and on again.
P.32
(EA)
Miswiring of indoor/outdoor unit
connecting wire (converse wiring
or disconnection)
―
P.32
(Eb)
Startup time over
―
P.32
(EC)
2 blinking Indoor/outdoor unit communication
error signal receiving error) is
detected by indoor unit.
E6
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if noise entered into indoor/outdoor connecting wire or
power supply.
3
Check if noise entered into indoor/outdoor controller board.
4
Re-check error by turning off power, and on again.
*2
Indoor/outdoor unit communication
error (transmitting error) is
detected by indoor unit.
E7
*2
Indoor/outdoor unit communication
error (signal receiving error) is
detected by outdoor unit.
―
P.38
(E8)
Indoor/outdoor unit communication
error (transmitting error) is
detected by outdoor unit.
―
P.38
(E9)
3 blinking Remote controller signal receiving
error is detected by remote
controller.
E0
1
Check if connecting wire of indoor unit or remote controller is
connected correctly.
2
Check if noise entered into transmission wire of remote controller.
3
Re-check error by turning off power, and on again.
P.37
Remote controller transmitting
error is detected by remote
controller.
E3
P.37
Remote controller signal receiving
error is detected by indoor unit.
E4
P.37
Remote controller transmitting
error is detected by indoor unit.
E5
P.37
4 blinking Check code is not defined.
EF
1
Check if remote controller is MA remote controller(PAR-21MAA).
2
Check if noise entered into transmission wire of remote controller.
3
Check if noise entered into indoor/outdoor connecting wire.
4
Re-check error by turning off power, and on again.
P.38
PL
1
Be sure to replace the 4-way valve.
2
Check refrigerant pipes for disconnection or leakage.
3
After the recovery of refrigerant, vacuum dry the whole refrigerant circuit.
4
Refer to “10-6. HOW TO CHECK THE PARTS”.
5
Check refrigerant circuit for operation.
P.39
(2) Abnormal condition
*1 Check code displayed on remote controller
*2 Refer to the indoor unit service manual.
Continue to the next page
OCH636A