Check code Abnormal points and detection method
Case
judgment and action
U9
(4220)
Detailed
codes
To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2, and 2-6.
Refer to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".
01
Overvoltage error
• Increase in DC bus voltage to:
A12, 18N: 400 V
A24, 30, 36, 42N
:
430 V
1
Abnormal increase in power
source voltage
2
Disconnection of compressor
wiring
3
Defective outdoor power circuit
board
4
Compressor has a ground fault.
1
Check the field facility for the power supply.
2
Correct the wiring (U.V.W phase) to
compressor. Refer to "10-9. TEST POINT
DIAGRAM" (Outdoor power circuit board).
3
Replace outdoor power circuit board.
4
Check compressor for electrical insulation.
Replace compressor.
02
Undervoltage error
• Instantaneous decrease in DC
bus voltage to 200 V
1
Decrease in power source
voltage, instantaneous stop.
2
Defective converter drive circuit
in outdoor power circuit board
3
Defective 52C drive circuit in
outdoor power circuit board
4
Disconnection or loose
connection of CN2 on the
outdoor power circuit board/
controller circuit board
5
Power circuit failure on DC
supply for 15 V DC output on
outdoor controller circuit board
1
Check the field facility for the power supply.
2
Replace outdoor power circuit board.
3
Replace outdoor power circuit board.
4
Check CN2 wiring.
5
Replace outdoor controller circuit board.
04
Input current sensor error
• Decrease in input current
through outdoor unit to 0.1 A
only if operation frequency is
more than or equal to 40 Hz
or compressor current is more
than or equal to 6 A.
1
Defective input current
detection circuit in outdoor
power circuit board
2
Defective outdoor controller
circuit board
1
Replace outdoor power circuit board.
2
Replace outdoor controller circuit board.
08
Abnormal power synchronous
signal
• No input of power
synchronous signal to power
circuit board
• Power synchronous signal
of 44 Hz or less, or 65 Hz or
more is detected on power
circuit board.
1
Distortion of power source
voltage, noise superimposition
2
Disconnection or loose
connection of earth wiring
3
Disconnection or loose
connection of CN2 on the
outdoor power circuit board/
controller circuit board
4
Defective power synchronous
signal in outdoor controller
circuit board
5
Defective power synchronous
signal circuit in outdoor power
circuit board
1
Check the field facility for the power supply.
2
Check earth wiring.
3
Check CN2 wiring. (A24–42N only)
4
Replace outdoor controller circuit board.
5
Replace outdoor power circuit board.
(A24–42N only)
10
PFC error (Overvoltage/
Undervoltage/Overcurrent)
• PFC detected any of the fol-
lowing:
a) Increase of DC bus voltage
as follows:
A12, 18N: 400 V
A24, 30, 36, 42N
:
430 V
b) Decrease in PFC control
voltage to 13 V DC or lower
(A24–42N only)
c) Increase in input current as
follows:
A12, 18N: 50 A peak
A24, 30N: 42 A peak
A36, 42N: 62 A peak
1
Abnormal increase in power
source voltage
2
Decrease in power source
voltage, instantaneous stop
3
Disconnection of compressor
wiring
4
Misconnection of reactor (DCL)
5
Defective outdoor power circuit
board
6
Defective reactor (DCL)
7
Disconnection or loose
connection of CN2 on the
outdoor power circuit board/
controller circuit board
12
Check the field facility for the power supply.
3
Correct the wiring (U·V·W phase) to
compressor. Refer to "10-9. TEST POINT
DIAGRAM".
4
Correct the wiring (U·V·W phase) or reactor
(DCL). (A24–42N only)
5
Replace outdoor power circuit board.
6
Replace reactor (DCL). (A24–42N only)
7
Check CN2 wiring. (A24–42N only)
OCH636A