9
Service Ref.
PUY-A12NKA7
PUY-A12NKA7-BS
PUY-A18NKA7
PUY-A18NKA7-BS
PUY-A24NHA7
PUY-A12NHA7-BS
PUY-A30NHA7
PUY-A30NHA7-BS
PUY-A36NKA7
PUY-A36NKA7-BS
PUY-A42NKA7
PUY-A42NKA7-BS
Power
supply
Phase
Single
Cycle
60 Hz
Voltage
208/230 V
MCA
A
11
11
19
19
25
25
MOCP
A
28
28
26
26
31
31
Breaker size
A
15
15
25
25
30
30
External finish
Munsell 3Y 7.8/1.1
Heat exchanger
Cross fin
Defrost method
Reverse cycle
Crankcase heater
kW
―
Compressor
Hermetic
Model
SNB092FNCM
SNB130FBCM2
SNB172FWHM1
SNB172FWHM1
MNB33FBRMC-L MNB33FBRMC-L
Motor output
kW
0.65
0.9
1.2
1.2
2.5
2.5
R.L.A
7
7
7
7
8
8
L.R.A
12
12
11
11
13
13
Starter type
Inverter
Fan
Fan (drive) × No.
Propeller fan × 1
Propeller fan × 1
Propeller fan × 1
Propeller fan × 1
Propeller fan × 2
Propeller fan × 2
Fan motor output
kW
0.046
0.046
0.086
0.086
0.074 + 0.074
0.074 + 0.074
Fan motor
F.L.A
0.5
0.5
0.4
0.4
0.50 + 0.50
0.50 + 0.50
Air flow
CFM
1,590
1,590
1,940
1,940
3,880
3,880
K
/min
45
45
55
55
110
110
Sound
pressure level
Cooling
dB
44
44
47
47
52
52
Heating
dB
―
―
―
―
―
―
Protection devices
HP switch
HP switch
HP switch
HP switch
HP switch
HP switch
Comp. shell thermo Comp. shell thermo Comp. shell thermo Comp. shell thermo Comp. shell thermo Comp. shell thermo
Dimension
W
inch
31-13/16 + 2-7/16 31-13/16 + 2-7/16
37-12/32
37-12/32
41-5/16
41-5/16
D
inch
11-3/16
11-3/16
13 + 1-3/16
13 + 1-3/16
13 + 1-3/16
13 + 1-3/16
H
inch
24-13/16
24-13/16
37-1/8
37-1/8
52-11/16
52-11/16
W
mm
809 + 62
809 + 62
950
950
1050
1050
D
mm
300
300
330 +30
330 +30
330 + 30
330 + 30
H
mm
630
630
943
943
1338
1338
Weight
lb
92
99
151
151
211
211
kg
41
44
68
68
96
96
Refrigerant
R410A
R410A
R410A
R410A
R410A
R410A
Charged
lb
4 + 7/16
4 + 14/16
7 + 11/16
7 + 11/16
10 + 6/16
10 + 6/16
kg
2.0
2.2
3.5
3.5
4.7
4.7
Control
Linear expansion valve
Oil charged
Model
Ether (FV50S)
oz
12
16
23
23
45
45
L
0.35
0.5
0.7
0.7
1.4
1.4
Refrigerant
piping
Pipe size OD liquid
inch
1/4
1/4
3/8
3/8
3/8
3/8
mm
6.35
6.35
9.52
9.52
9.52
9.52
Pipe size OD gas
inch
1/2
1/2
5/8
5/8
5/8
5/8
mm
12.7
12.7
15.88
15.88
15.88
15.88
Connection method - Indoor
Flared
Connection method - Outdoor
Flared
Height difference
IU-OU
ft
Maximum 100
m
Maximum 30
Piping length
ft
Maximum 165
Maximum 165
Maximum 225
Maximum 225
Maximum 225
Maximum 225
m
Maximum 50
Maximum 50
Maximum 69
Maximum 69
Maximum 69
Maximum 69
OCH636A
Summary of Contents for PUY-A12NKA7