64
(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Operation mode
Remarks
COOL
HEAT
Intake temperature (TH1)
81°F [27
:
]
69°F [20.5
:
]
Indoor fluid pipe temperature (TH2)
41°F [5
:
]
113°F [45
:
]
Indoor 2-phase pipe temperature (TH5)
41°F [5
:
]
122°F [50
:
]
Set temperature
77°F [25
:
]
72°F [22
:
]
Outdoor liquid pipe temperature (TH3)
113°F [45
:
]
41°F [5
:
]
(*1)
Outdoor 2-phase pipe temperature (TH6)
122°F [50
:
]
41°F [5
:
]
(*1)
Outdoor air temperature (TH7)
95°F [35
:
]
45°F [7
:
]
(*1)
Outdoor suction (TH32)
41°F [5
:
]
41°F [5
:
]
(*2)
Temperature difference code
(intake temperature
−
set temperature) (∆Tj)
5
5
Discharge super heat (SHd)
54°F [30
:
]
54°F [30
:
]
(*2)
Sub-cool (SC)
9°F [5
:
]
9°F [5
:
]
(*2)
*1 If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors to open/short.
And the unit runs emergency operation with the values listed above.
*2 If one thermistor is set to open/short, the values of SHd/SC will be different from the list above.
[Example] When liquid temperature thermistor (TH3) has an open or short circuit.
Thermistor
COOL
HEAT
TH3
113°F [45
:
]
41°F [5
:
]
TH6
Ta
Tb
Regard normal figure as effective data.
TH4
Tc
Td
Regard normal figure as effective data.
TH5
41°F [5
:
]
122°F [50
:
]
TH2
41°F [5
:
]
113°F [45
:
]
TH33
Regard normal figure as effective data.
Discharge superheat (SHd)
Cooling = TH4−TH6 = Tc−Ta
Heating = TH4−TH5 = Td−122°F [50
:
]
Degree of subcooling (SC)
Cooling = TH6−TH3 = Ta−113°F [45
:
]
Heating = TH5−TH2 = 50
:
−45
:
= 5˚C
or
= 122°F−113°F = 9˚F
OCH636A