78
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
The number of connected indoor
units
0 to 3
(The number of connected indoor units are displayed.)
Unit
1
ON
2 3 4 5 6
Capacity setting display
Displayed as an outdoor capacity code
Capacity
A12N
A18N
A24N
A30N
A36N
A42N
Code
9
10
11
Capacity Code
14
20
25
Code
display
1
ON
2 3 4 5 6
Outdoor unit setting information
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 :
3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump, 3 phase and
defrosting (normal) are set up, “20” is
displayed.
Code
display
1
ON
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2(1))
Indoor 1
−38 to 190
−38 to 190 [−39 to 88
:
]
(When the temperature is 0ºF or less, “–” and
temperature are displayed by turns.)
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor pipe temperature/Cond./
Eva. (TH5(1))
Indoor 1
−38 to 190
−38 to 190 [−39 to 88
:
]
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2(2))
Indoor 2
−38 to 190
−38 to 190 [−39 to 88
:
]
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor pipe temperature/Cond./
Eva. (TH5(2))
Indoor 2
−38 to 190
−38 to 190 [−39 to 88
:
]
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor room temperature (TH1)
46 to 102
Indoor room temperature (TH1)
46 to 102
˚F
[
:
]
The black square (
■
) indicates a switch position.
OCH636A
Summary of Contents for PUY-A12NKA7
Page 119: ...119 OCH636A ...