32
Check code Abnormal points and detection method
Case
judgment and action
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open for
3 minutes continuously after power supply.
63H: High-pressure switch
1
Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2
Disconnection or contact failure
of 63H
3
63H is working due to defective
parts.
4
Defective outdoor controller
circuit board
1
Check connection of 63H connector on
outdoor controller circuit board.
Refer to "10-9. TEST POINT DIAGRAM".
2
Check the 63H side of connecting wire.
3
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.
EA
(6844)
Miswiring of indoor/outdoor unit
connecting wire
1. Outdoor controller circuit board can
automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automatically
due to miswiring of indoor/outdoor unit
connecting wire, etc. after power is
turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
board recognizes excessive number of
indoor units.
1
Contact failure or miswiring of
indoor/outdoor unit connecting wire
2
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
3
Excessive number of indoor
units are connected to 1 indoor
unit. (4 units or more)
4
Defective transmitting receiving
circuit of outdoor controller
circuit board
5
Defective transmitting receiving
circuit of indoor controller board
6
Defective indoor power board
7
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
8
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
1
Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of
indoor and outdoor units.
2
Check diameter and length of indoor/outdoor
unit connecting wire.
Total wiring length: 262 ft [80 m]
(including wiring connecting each indoor unit
and between indoor and outdoor unit)
Also check if the connection order of flat cable
is S1, S2, S3.
3
Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected)
4
–
6
Turn the power off once, and on again to
check.
Replace outdoor controller circuit board,
indoor controller board or indoor power
board if abnormality occurs again.
7
Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board) are
overlapping in case of group control system.
8
Check transmission path, and remove the
cause.
Note: The descriptions above,
1
–
8
, are for EA,
Eb and EC.
Eb
(6845)
Miswiring of indoor/outdoor unit
connecting wire (converse wiring or
disconnection)
Outdoor controller circuit board can
automatically set the unit number of indoor
units.
Abnormal if the indoor unit number can-
not be set within 4 minutes after power on
because of miswiring (converse wiring or
disconnection) of indoor/outdoor unit con-
necting wire.
1
Contact failure or miswiring of
indoor/outdoor unit connecting wire
2
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
4
Defective transmitting receiving cir-
cuit of outdoor controller circuit board
5
Defective transmitting receiving
circuit of indoor controller board
6
Defective indoor power board
7
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
8
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
EC
(6846)
Startup time over
The unit cannot finish Startup process with-
in 4 minutes after power on.
1
Contact failure of indoor/
outdoor unit connecting wire
2
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
7
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
8
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
OCH636A
Summary of Contents for PUY-A12NKA7
Page 119: ...119 OCH636A ...