GB-40
WT07282X01
・
When the piping length from the outdoor unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
additional
charge (oz)
=
High-pressure pipe
ø1-1/8 total length
× 3.54 (oz/ft)
+
High-pressure pipe
ø7/8 total length
× 2.26 (oz/ft)
+
High-pressure pipe
ø3/4 total length
× 1.51 (oz/ft)
+
High-pressure pipe
ø5/8 total length
× 1.08 (oz/ft)
+
Liquid pipe ø5/8
total length
× 1.94 (oz/ft)
+
Liquid pipe ø1/2
total length
× 1.19 (oz/ft)
+
Liquid pipe ø3/8
total length
× 0.59 (oz/ft)
+
Liquid pipe ø1/4
total length
× 0.23 (oz/ft)
+
Total capacity of
outdoor units
Amount (oz)
(to be added for standard or
main BC controller)
+
Main BC controller
Amount (oz)
200
106
HA-type
71
250
160
300
160
350–900
212
+
Number of sub BC
controllers
Amount (oz)
(to be added for sub
BC controller)
+
Total capacity of connected
indoor units
Amount (oz)
(to be added for
indoor unit)
1
35
80 or below
71
2
71
81 to 160
89
161 to 330
106
331 to 390
124
391 to 480
159
481 to 630
177
631 to 710
212
711 to 800
283
801 to 890
318
891 to 1070
353
1071 to 1250
424
1251 or above
494
Outdoor unit model
Amount (oz)
(to be added for
outdoor unit)
Single
P200 to P250
0
P300 to P400
0
P450 to P500
195
Combination
P400 to P550
0
P600 to P800
0
P850
195
+
P900
389
Single
EP200 to EP250
0
EP300 to EP350
0
EP400 to EP500
35
Combination
EP500 to EP550
0
EP600 to EP700
0
EP750
35
EP800 to EP900
70