GB-36
WT07282X01
(1) Units "m" and "kg" (In an R2 system)
<Formula>
・
When the piping length from the outdoor unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
additional
charge (kg)
=
High-pressure pipe
ø28.58 total length
× 0.36 (kg/m)
+
High-pressure pipe
ø22.2 total length
× 0.23 (kg/m)
+
High-pressure pipe
ø19.05 total length
× 0.16 (kg/m)
+
High-pressure pipe
ø15.88 total length
× 0.11 (kg/m)
+
Liquid pipe ø15.88
total length
× 0.2 (kg/m)
+
Liquid pipe ø12.7
total length
× 0.12 (kg/m)
+
Liquid pipe ø9.52
total length
× 0.06 (kg/m)
+
Liquid pipe ø6.35
total length
× 0.024 (kg/m)
+
Total capacity of
outdoor units
Amount (kg)
(to be added for standard or
main BC controller)
+
Main BC controller
Amount (kg)
200
3.0
HA-type
2.0
250
4.5
300
4.5
350–900
6.0
+
Number of sub BC
controllers
Amount (kg)
(to be added for sub
BC controller)
+
Total capacity of connected
indoor units
Amount (kg)
(to be added for
indoor unit)
1
1.0
80 or below
2.0
2
2.0
81 to 160
2.5
161 to 330
3.0
331 to 390
3.5
391 to 480
4.5
481 to 630
5.0
631 to 710
6.0
711 to 800
8.0
801 to 890
9.0
891 to 1070
10.0
1071 to 1250
12.0
1251 or above
14.0
+
Outdoor unit model
Amount (kg)
(to be added for
outdoor unit)
Single
P200 to P250
0
P300 to P400
0
P450 to P500
5.5
Combination
P400 to P550
0
P600 to P800
0
P850
5.5
P900
11.0
Single
EP200 to EP250
0
EP300 to EP350
0
EP400 to EP500
1.0
Combination
EP500 to EP550
0
EP600 to EP700
0
EP750
1.0
EP800 to EP900
2.0
Summary of Contents for PURY-(E)P-YLM-A (-BS)
Page 2: ......
Page 62: ...GB 60 WT07282X01 ...