GB
GB-31
WT07282X01
9-5-3. Sealing the openings around the pipes
Seal all openings around pipes and wires to keep out small animals, rainwater, or snow.
-Failure to do so may result in current leakage, electric shock, or damage to the unit.
Ⓐ
Ⓑ
Ⓐ
Example of closure materials (not supplied)
Ⓑ
Fill the openings
9-6. Air-tightness test
Do not use oxygen, flammable gas, or a refrigerant containing chlorine for air-tightness
testing.
-Doing so may result in an explosion. Chlorine will deteriorate the refrigerant oil.
After refrigerant pipe installation is completed, check the system for leaks by conducting an air-tightness test. If there
is a leak, the composition of the refrigerant will change and the performance will drop.
<Air-tightness test procedures>
①
Make sure the service valves are closed.
②
Add pressure to the refrigerant pipes through the service ports of the high- and low-pressure pipes.
* Pressurize to the design pressure (4.15 MPa) using nitrogen gas.
③
If the pressure holds for one day and does not decrease, the pipes have passed the test and there are no leaks.
If the pressure decreases, there is a leak. Look for the source of the leak by spraying a bubbling agent (e.g.,
Gupoflex) on the flared or brazed sections.
④
Wipe off the bubbling agent.
LO
HI
Ⓐ
Ⓓ
Ⓔ
Ⓒ
Ⓑ
Ⓑ
Ⓗ
Ⓘ
Ⓙ
Ⓖ
Ⓕ
Ⓐ
Nitrogen gas
Ⓑ
To indoor unit
Ⓒ
Gauge manifold
Ⓓ
Low pressure knob
Ⓔ
High pressure knob
Ⓕ
Service valve
Ⓖ
Low-pressure pipe
Ⓗ
High-pressure pipe
Ⓘ
Outdoor unit
Ⓙ
Service port
* The figure shows a unit on which an outdoor unit twinning kit
(low-pressure side) is not installed.
Summary of Contents for PURY-(E)P-YLM-A (-BS)
Page 2: ......
Page 62: ...GB 60 WT07282X01 ...