GB-52
WT07282X01
10-6. Address setting
・
Set the address setting switch as follows.
Address setting method
Address
Indoor unit (Main, Sub)
Assign the lowest address to the main indoor unit in the group, and assign sequential
addresses to the rest of the indoor units in the same group.
* In an R2 system with a sub BC controller or in a Hybrid City Multi system with a
Sub-HBC, make the settings for the indoor units in the following order. (Set the
addresses so that the addresses of
①
are smaller than those of
②
, and the addresses
of
②
are smaller than those of
③
.)
①
Indoor units that are connected to the main BC controller or main HBC
controller
②
Indoor units that are connected to sub BC controller 1 or Sub-HBC
③
Indoor units that are connected to sub BC controller 2 or Sub-HBC
01 to 50
Outdoor unit (OC, OS)
Assign sequential addresses to the outdoor units in the same refrigerant system.
* To set the address to 100, the address setting switch must be set to 50.
51 to 100
BC controller
HBC controller
Sub-HBC
Main
Assign an address that equals the address of the outdoor unit plus 1. If the address that
is assigned to the main BC controller or the main HBC controller overlaps any of the
addresses that are assigned to the outdoor units or to the sub BC controller or the
Sub-HBC, use a different, unused address within the setting range.
* To set the address to 100, the address setting switch must be set to 50.
51 to 100
Sub
Assign an address that equals the lowest address of the indoor units that are connected
to the sub BC controller or the Sub-HBC plus 50.
* To set the address to 100, the address setting switch must be set to 50.
51 to 100
ME remote controller
Main
Assign an address that equals the address of the main indoor unit in the group plus 100.
101 to 150
Sub
Assign an address that equals the address of the main indoor unit in the group plus 150.
151 to 200
MA remote controller
Address setting is not required. (The Main/Sub setting is required.)
–
* The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. The outdoor units are designated as OC and OS
in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
* Make indoor unit group settings from remote controllers after turning on the power to all units.
Summary of Contents for PURY-(E)P-YLM-A (-BS)
Page 2: ......
Page 62: ...GB 60 WT07282X01 ...