9-9. Additional refrigerant charge
Charge refrigerant in a liquid state.
-Charging refrigerant in the gaseous state will change the composition of the refrigerant and lead
to a performance drop.
Do not use a charging cylinder when charging refrigerant.
-The use of a charging cylinder may change the composition of the refrigerant and lead to a
performance drop.
The amount of refrigerant that is shown in the table below is factory-charged in the outdoor units. The amount
necessary for extended piping is not included and needs to be added on site.
Unit model
Factory-charged amount [kg (oz)]
Unit model
Factory-charged amount [kg (oz)]
P200
9.5 (335)
EP200
8.5 (299)
P250
9.5 (335)
EP250
8.5 (299)
P300
10.3 (363)
EP300
9.3 (328)
P350
10.3 (363)
EP350
9.3 (328)
P400
10.3 (363)
EP400
11.8 (416)
P450
11.8 (416)
EP450
11.8 (416)
P500
11.8 (416)
EP500
11.8 (416)
The amount of refrigerant that is shown in the table below is the maximum amount to be added on site
.
Unit model
Maximum amount to be added [kg (oz)]
Unit model
Maximum amount to be added [kg (oz)]
P200YLM
27.5 (970)
EP200YLM
27.5 (970)
P250YLM
33.5 (1182)
EP250YLM
33.5 (1182)
P300YLM
37.0 (1305)
EP300YLM
37.0 (1305)
P350YLM
39.0 (1376)
EP350YLM
39.0 (1376)
P400YLM
45.0 (1587)
EP400YLM
45.0 (1587)
P400YSLM
52.0 (1834)
EP450YLM
49.0 (1728)
P450YLM
49.0 (1728)
EP500YLM
49.0 (1728)
P450YSLM
52.0 (1834)
EP500YSLM
52.0 (1834)
P500YLM
49.0 (1728)
EP550YSLM
59.0 (2081)
P500YSLM
52.0 (1834)
EP600YSLM
62.5 (2205)
P550YSLM
59.0 (2081)
EP650YSLM
75.0 (2646)
P600YSLM
62.5 (2205)
EP700YSLM
79.5 (2804)
P650YSLM
75.0 (2646)
EP750YSLM
79.5 (2804)
P700YSLM
79.5 (2804)
EP800YSLM
79.5 (2804)
P750YSLM
79.5 (2804)
EP850YSLM
84.0 (2963)
P800YSLM
79.5 (2804)
EP900YSLM
89.0 (3139)
P850YSLM
84.0 (2963)
P900YSLM
89.0 (3139)
Both refrigerant overcharge and undercharge will cause problems. Charge the system with the proper amount of
refrigerant.
Record the added refrigerant amount on the label attached to the control box panel for future servicing.
9-9-1. Calculation of the amount of additional refrigerant
・
The amount of refrigerant to be added depends on the size and the total length of the high-pressure piping and
liquid piping.
・
Calculate the amount of refrigerant to be charged according to the formula below.
・
Round up the calculation result to the nearest 0.1 kg (0.1 oz).
・
Refer to the HBC controller Installation Manual for the additional amount of refrigerant for a Hybrid City Multi
system.
・
The refrigerant does not need to be added for the indoor units in a Hybrid City Multi system.