<Reference> Size of refrigerant pipes
On-site piping [mm (in)]
Service valve piping [mm (in)]
High-pressure side
Low-pressure side
High-pressure side
Low-pressure side
P200
ø15.88 (ø5/8)
ø19.05 (ø3/4)
ø25.4 (ø1)
ø25.4 (ø1)
P250
ø19.05 (ø3/4)
ø22.2 (ø7/8)
P300
P350
ø28.58 (ø1-1/8)
P400
ø22.2 (ø7/8)
P450
ø28.58 (ø1-1/8)
P500
On-site piping [mm (in)]
Service valve piping [mm (in)]
High-pressure side
Low-pressure side
High-pressure side
Low-pressure side
EP200
ø15.88 (ø5/8)
ø19.05 (ø3/4)
ø25.4 (ø1)
ø28.58 (ø1-1/8)
EP250
ø19.05 (ø3/4)
ø22.2 (ø7/8)
EP300
EP350
ø28.58 (ø1-1/8)
EP400
ø22.2 (ø7/8)
EP450
EP500
<Reference> Severed section
Ⓒ
Ⓑ
Ⓐ
Ⓐ
75 mm (3 in) (reference)
Ⓑ
Pipe section to be cut (Use a pipe cutter.)
Ⓒ
Service valve side
・
When expanding the on-site piping, satisfy the minimum insertion depth requirement as follows.
Pipe size [mm (in)]
Minimum insertion depth [mm (in)]
ø5 (ø1/4) or more, less than ø8 (ø13/8)
6 (1/4)
ø8 (ø13/8) or more, less than ø12 (ø1/2)
7 (5/16)
ø12 (ø1/2) or more, less than ø16 (ø11/16)
8 (3/8)
ø16 (ø11/16) or more, less than ø25 (ø1)
10 (7/16)
ø25 (ø1) or more, less than ø35 (ø1-7/16)
12 (1/2)
ø35 (ø1-7/16) or more, less than ø45 (ø1-13/16)
14 (9/16)