IX
Troubleshooting ]
- 246 -
HWE0804A
GB
(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the INV
board error
detection cir-
cuit.
<P72 and P96 models>
1)
IPM/overcurrent breaker trip
Error code: 4250
Detail code: No. 101, 104, 105, 106,
and 107
Replace the INV board.
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
2)
Logic error
Error code: 4220
Detail code: No. 111
Replace the INV board.
(2)
Put the outdoor unit
into operation.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
4)
IPM open
Error code: 5301
Detail code: No.119
Normal
<P120 model>
1)
IPM/overcurrent breaker trip
Error code: 4250
Detail code: No. 101, 102, 103, 104,
105, 106, and 107
See the section "Troubleshooting
the IPM" ( Refer to - 6 - [5] ).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
(1)
Disconnect the invert-
er output wire from
the output terminals
(U, V, W) of the IPM.
2)
Logic error
Error code: 4220
Detail code: No. 111
See the section "Troubleshooting
the IPM" ( Refer to - 6 - [5] ).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
Replace the INV board, and put
the outdoor unit back into opera-
tion.
If the problem persists, replace the
DCCT.
(2)
Put the outdoor unit
into operation.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
4)
DCCT sensor circuit failure
Error code: 5301
Detail code: No.118
Replace the DCCT board.
Replace the DCCT, and put the
outdoor unit back into operation.
If the problem persists, replace the
INV board.
5)
IPM open
Error code: 5301
Detail code: No.119
Normal
[2]
Check for
compressor
ground fault or
coil error.
Disconnect the compres-
sor wiring, and check the
compressor Meg, and coil
resistance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
When no liquid refrigerant in the
compressor
Replace the compressor
Check that no liquid refrigerant in
the compressor.
2)
Compressor coil resistance failure
Coil resistance value of 0.3 ohm
(20°C [68°F]) : -P96 models
Coil resistance value of 0.3 ohm
(20°C [68°F]) : P120 model
[THMU-A]
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......