1. Error
Code
Instantaneous overcurrent (Detail code 106)
Overcurrent (Detail code 107)
2. Error definition and error detection method
P72 and P96 models
Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor.
P120 model
Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.
3. Cause, check method and remedy
Refer to section -6- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 252)
1. Error
Code
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.
4250
(YHMU-A)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -6- (2) [1] - [4].(page 254)
Check the IGBT module resistance value of the INV board, if no
problems are found.
(Refer to the Trouble shooting for IGBT module)
4250
4255
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to IX [4] -6- (2) [2].
(2)
Inverter output related
Refer to IX [4] -6- (2) [1] - [4].
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to IX [4] -6- (2) [5].
(2)
Fan board failure
Refer to IX [4] -6- (2) [6].
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......