[
VIII
Test Run Mode ]
- 142 -
HWE0804A
GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-P264TSHMU-A
PUHY-P72THMU-A
PUHY-P72THMU-A
PUHY-
P120THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion
6
Model
-
36/36/48/48/48/48
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
31 [ 68]
Outdoor
unit
Electric current
A
59.2
Voltage
V
230
Compressor frequency
Hz
53
53
77
LEV open-
ing
Indoor unit
Pulse
332/332/406/406/406/406
SC (LEV1)
0
0
0
LEV2
1400
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.63/0.66
2.63/0.66
2.63/0.66
[381/96]
[381/96]
[381/96]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
72 [162]
72 [162]
70 [158]
Heat exchanger out-
let (TH3)
0 [32]
0 [32]
-1 [30]
Accumulator inlet
0 [32]
0 [32]
-1 [30]
Accumulator outlet
0 [32]
0 [32]
-1 [30]
Compressor inlet
0 [32]
0 [32]
-1 [30]
Compressor shell
bottom
40 [104]
40 [104]
40 [104]
Indoor
unit
LEV inlet
36 [97]
36 [97]
36 [97]
Heat exchanger
inlet
70 [158]
70 [158]
69 [156]
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......