IX
Troubleshooting ]
- 211 -
HWE0804A
GB
1. Error
Code
Capacity code setting error
2. Error definition and error detection method
Connection of incompatible (wrong capacity code) indoor unit or outdoor unit
3. Error source, cause, check method and remedy
7101
Error source
Cause
Check method and remedy
Outdoor unit
Indoor unit
(1)
The model name (capacity code) set by
the switch (SW2) is wrong.
1)
Check the model name (capacity code) of the in-
door unit which has the error source address set by
the switch (SW2 on indoor unit board).
When the model name set by the switch is different
from that of the unit connected, turn off the power
source of the outdoor and the indoor units, and
change the setting of the capacity code.
*The capacity of the indoor unit can be
confirmed by the self-diagnosis function
(SW1 operation) of the outdoor unit.
Outdoor unit
(2)
The model selection switches (SW5-1 -
5-4) on the outdoor unit are set incor-
rectly.
Check the setting for the model selection switch on
the outdoor unit (Dipswitches SW5-1 - 5-4 on the
outdoor unit control board).
72 model
96 model
120 model
SW5
OFF
ON OFF OFF
ON
ON OFF OFF
OFF OFF ON
OFF
1
2
3
4
Model
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......